Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

F-25

F-25

TROUBLESHOOTING & REPAIR

MAIN TRANSFORMER (T1) VOLTAGE TEST (continued)

FIGURE F.8 - TERMINAL STRIP

14 PIN MS RECEPTACLE

POSITIVE

 

LOW INDUCTANCE

HIGH INDUCTANCE

OUTPUT

 

NEGATIVE OUTPUT

NEGATIVE OUTPUT

TERMINAL

TERMINAL STRIP

TERMINAL

TERMINAL

 

COVER PANEL

 

 

+21 -21 41 4

2

31 32

75 76 77

TERMINAL STRIP

Return to Section TOC

Return to Master TOC

10.Test for 115 VAC between leads #31 and #32 on the terminal strip. The terminal strip can be accessed by removing the small panel at the lower portion of the case front. See Figure F.8. 115 VAC AC should also be present at the 115 VAC receptacle. If the correct voltage is not present, make sure the 20 amp circuit breaker is not tripped or faulty. Also check the wiring between the main transformer, the terminal strip, the cir- cuit breaker and the receptacle. See the Wiring Diagram.

11.If 115 VAC is NOT present and the wiring and circuit breaker are good, the main transformer may be defective.

12.Test for 42 VAC between leads #41 and #2 on the terminal strip. The terminal strip can be accessed by removing the small panel at the lower portion of the case front. See Figure F.8. If the correct voltage is not pre- sent, make sure the 10 amp circuit breaker is not tripped or faulty. Also check the wiring between the main transformer, the terminal strip, and the circuit breaker. See the Wiring Diagram.

13.Remove the AC input power to the DC- 655. Remove the screws from the control box cover and carefully lower the cover.

14.Locate the firing board on the left side of the control box.

Return to Section TOC

Return to Master TOC

IDEALARC DC-655

Page 67
Image 67
Lincoln Electric DC-655 service manual Figure F.8 Terminal Strip