NCR 7870 manual European Checkstand Wiring, 220Vac Store

Models: 7870

1 228
Download 228 pages 15.5 Kb
Page 53
Image 53

Chapter 3: Site Preparation 3-11

European Checkstand Wiring

Use this diagram when line voltage to the Service Panel is 220 Vac and European double-pole circuit breakers are used in the Distribution Panel.

220Vac Store

Load Center

L3

Circuit A

Belt Control

Neutral and

N

Lighting

Belt

Ground Bus

N

G

Conduit

Misc. Equip.

Motor

Checkstand

Frame

Feeder wiring and insulated ground from main service panel to distribution panel to be run in metal conduit.

The electrical wiring must meet state and local electrical codes, laws, and regulations.

Isolated/

Insulated

Ground Bus.

L2 L1

European double-pole circuit breakers.

NCR circuits should be run in seprate metal Conduits.

220 Vac

Neutral Bus

Distribution Panel

Circuit B

Terminal

Circuit C

Scanner/Scale

Isolated Ground Receptacles

Note :

NCR circuits must be dedicated to NCR equipment or other logically connected electronic equipment (modems, DAA, bridges, etc.)

R0133

Page 53
Image 53
NCR 7870 manual European Checkstand Wiring, 220Vac Store