3-12 Chapter 3: Site Preparation

International Checkstand Wiring

Use this diagram when the line voltage to the Service Panel is 220 or 240 Vac and standard single pole circuit breakers are used in the Distribution Panel.

240220 Vac

Main Service

Panel

 

L3

Circuit A

Belt Control

Neutral and

N

Lighting

Belt

Ground Bus

N

G

Conduit

Misc. Equip.

Motor

Checkstand

Frame

Feeder wiring and insulated ground from main service panel to distribution panel to be run in metal conduit.

The electrical wiring must meet state and local electrical codes, laws, and regulations.

Isolated/

Insulated

Ground Bus.

L2 L1

Standard single-pole circuit breakers.

NCR circuits should be run in seprate metal Conduits.

220

230 Vac

240

Neutral Bus

Distribution Panel

Circuit B

Terminal

Circuit C

Scanner/Scale

Isolated Ground Receptacles

Note :

NCR circuits must be dedicated to NCR equipment or other logically connected electronic equipment (modems, DAA, bridges, etc.)

R0134