Technical data of CPU 31xC 6.3 CPU 313C

Technical data

Timers/counters and their retentivity

S7 counters

256

Retentive memory

Configurable

Default

from C0 to C7

Counting range

0 to 999

IEC Counters

Yes

Type

SFB

Number

unlimited (limited only by RAM size)

S7 timers

256

Retentive memory

Configurable

Default

Not retentive

Timer range

10 ms to 9990 s

IEC Timers

Yes

Type

SFB

Number

unlimited (limited only by RAM size)

Data areas and their retentivity

 

Flag bits

256 bytes

Retentive memory

Configurable

Default retentivity

MB0 to MB15

Clock flag bits

8 (1 byte per flag bit)

Data blocks

Max. 511

 

 

(DB 1 to DB 511)

Length

max. 16 KB

Local data per priority class

max. 510 bytes

Blocks

 

Total

1024 (DBs, FCs, FBs)

 

 

The maximum number of blocks that can be

 

 

loaded may be reduced if you are using another

 

 

MMC.

OBs

see the Instruction List

Length

max. 16 KB

Nesting depth

 

Per priority class

8

additional within an error OB

4

FBs

Max. 512

 

 

(FB 0 to FB 511)

Length

max. 16 KB

FCs

Max. 512

 

 

(FC 0 to FC 511)

Length

max. 16 KB

CPU 31xC and CPU 31x, Technical data

6-9

Manual, Edition 08/2004, A5E00105475-05

Page 119
Image 119
Siemens S7-300 appendix Technical data Timers/counters and their retentivity, Data areas and their retentivity