Siemens S7-300 appendix Technical data Data areas and their retentivity

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 180
Image 180

Technical data of CPU 31x 7.4 CPU 315-2 DP

Technical data

Data areas and their retentivity

Flag bits

2048 bytes

Retentive memory

Yes

Default retentivity

MB0 to MB15

Clock flag bits

8 (1 byte per flag bit)

Data blocks

 

Number

1023

 

 

(DB 1 to DB 1023)

Length

16 KB

Local data capacity

Max. 1024 bytes per task/510 per block

Blocks

 

Total

1024 (DBs, FCs, FBs)

 

 

The maximum number of blocks that can be

 

 

loaded may be reduced if you are using another

 

 

MMC.

OBs

See the Instruction List

Length

16 KB

Nesting depth

 

Per priority class

8

additional within an error OB

4

FBs

See the Instruction List

Number

2048

 

 

(FB 0 to FB 2047)

Length

16 KB

FCs

See the Instruction List

Number

2048

 

 

(FC 0 to FC 2047)

Length

16 KB

Address areas (I/O)

 

Total I/O address area

max. 2048 bytes/2048 bytes

 

 

(can be freely addressed)

Distributed

Max. 2000

I/O process image

128/128

Digital channels

Max. 16384

of those local

Max. 1024

Analog channels

Max. 1024

of those local

Max. 256

Assembly

 

Racks

Max. 4

Modules per rack

8

Number of DP masters

 

Integrated

1

via CP

1

7-14

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 180
Image 180
Siemens S7-300 appendix Technical data Data areas and their retentivity