Technical data of CPU 31x 7.4 CPU 315-2 DP

Technical data

Diagnostic buffer

Yes

Number of entries (not configurable)

Max. 100

Communication functions

 

PG/OP communication

Yes

Global data communication

Yes

Number of GD circuits

8

Number of GD packets

Max. 8

 

Sending stations

Max. 8

 

Receiving stations

Max. 8

Length of GD packets

max. 22 bytes

 

Consistent data

22 bytes

S7 basic communication

Yes

User data per request

max. 76 bytes

 

Consistent data

76 bytes (for X_SEND or X_RCV)

 

 

 

64 bytes (for X_PUT or X_GET as the server)

S7 communication

Yes

As server

Yes

as client

Yes (via CP and loadable FBs)

User data per request

Max. 180 bytes (with PUT/GET)

 

Consistent data

64 byte (as the server)

S5-compatible communication

Yes (via CP and loadable FCs)

Number of connections

16

can be used for

 

PG communication

Max. 15

 

Reserved (default)

1

 

Configurable

1 to 15

OP communication

Max. 15

 

Reserved (default)

1

 

Configurable

1 to 15

S7-based communication

Max. 12

 

Reserved (default)

12

 

Configurable

0 to 12

Routing

Yes (max. 4)

Interfaces

 

1st interface

 

Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

No

Interface power supply

max. 200 mA

(15 to 30 VDC)

 

7-16

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 182
Image 182