Siemens S7-300 appendix System status lists SSLs in Profinet IO Chapter Content, Applicability

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 51
Image 51

Communication 3.2 Communication services

3.2.10.3System status lists (SSLs) in PROFINET IO

Chapter Content

This chapter explains the following:

Which SSLs are intended for PROFINET

Which SSLs are intended for PROFIBUS DP

Which SSLs are intended for both PROFINET IO and PROFIBUS DP

Compatibility of the new SSLs

For PROFINET IO, it was necessary to create some new SSLs, among other things, because larger configurations are now possible with PROFINET.

You can also use these new SSLs with PROFIBUS.

You can continue to use a known PROFIBUS SSL that is also supported by PROFINET. If you use an SSL in PROFINET that does not support PROFINET, an error code is returned in RET_VAL (8083: Index wrong or not permitted).

Comparison of the System Status Lists of PROFINET and PROFIBUS

Table 3-9

Comparison of the System Status Lists of PROFINET and PROFIBUS

 

 

 

 

 

SSL-ID

 

PROFINET IO

PROFIBUS DP

Applicability

W#16#0591

 

yes

Yes

Module status information for the interfaces of a

 

 

(parameter adr1 changed)

 

module/submodule

W#16#0A91

 

yes

Yes

Status information of all subsystems and master

 

 

(parameter adr1 changed)

 

systems (S7-300 without CPU 318-2 DP)

W#16#0C91

 

yes

Yes

Module status information of a module/submodule in a

 

 

(parameter adr1/adr2 and

 

central configuration or attached to an integrated DP or

 

 

expected/actual type ID

 

PN interface module using the logical address of the

 

 

changed)

 

module.

W#16#4C91

 

yes

Yes

Not with S7-300

 

 

(parameter adr1 changed)

 

Module status information of a module/submodule

 

 

 

 

attached to an external DP or PN interface module

 

 

 

 

using the start address

W#16#0D91

 

yes

Yes

Module status information of all modules in the

 

 

(parameter adr1 changed)

 

specified rack/station

new:

 

Yes

Yes

Module status information of all submodules of a

W#16#0696

 

 

 

module using the logical address of the module, not

 

 

 

 

possible for submodule 0

new:

 

Yes

Yes

Module status information of a submodule using the

W#16#0C96

 

 

 

logical address of this submodule

W#16#xy92

 

No

Yes

Rack/stations status information

 

 

(replacement: SSL-ID

 

Replace this SSL with the SSL with the ID W#16#xy94

 

 

W#16#0x94)

 

in PROFIBUS DP as well.

new:

 

Yes

Yes

Rack/station status information

W#16#0x94

 

 

 

 

CPU 31xC and CPU 31x, Technical data

3-23

Manual, Edition 08/2004, A5E00105475-05

Page 51
Image 51
Siemens S7-300 System status lists SSLs in Profinet IO Chapter Content, Compatibility of the new SSLs, Applicability