Cycle and reaction times

5.4 Calculating method for calculating the cycle/response time

Response time

Table 5-12 Calculating the response time

Shortest response time

Longest response time

-

Multiply the physical cycle time by factor 2.

Now add I/O delay.

Now add the I/O delay plus the DP cycle times on

 

PROFIBUS-DP or the PROFINET IO update

 

times.

The result is the shortest response time.

The result is the longest response time.

See also

Longest response time (Page 5-17)

Shortest response time (Page 5-16)

Calculating the cycle time (Page 5-5)

Cycle extension through component-based automation (CBA) (Page 5-11)