Technical data of CPU 31xC 6.6 Technical data of the integrated I/O

6.6.4Interrupts

Interrupt inputs

All digital inputs of the on-board I/O of CPUs 31xC can be used as interrupt inputs.

You can specify interrupt behavior for each individual input in your parameter declaration. Options are:

no interrupt

Interrupt at the positive edge

Interrupt at the negative edge

Interrupt at the positive and negative edge

Note

Every channel will hold one event if the rate of incoming interrupts exceeds the handling capacity of OB40. Further events (interrupts) will be lost, without diagnostics or explicit message.

Start information for OB40

The table below shows the relevant temporary variables (TEMP) of OB40 for the interrupt inputs of 31xC CPUs. A description of process interrupt OB 40 is found in the Reference Manual System and Standard Functions.

Table 6-11 Start information for OB40, relating to the interrupt inputs of the integrated I/O

Byte

Variables

Data type

 

Description

6/7

OB40_MDL_ADDR

WORD

B#16#7C

Address of the interrupt-

 

 

 

 

triggering module (here: default

 

 

 

 

addresses of the digital inputs)

8 on

OB40_POINT_ADDR

DWORD

see the figure

Displaying the interrupt-

 

 

 

below

triggering integrated inputs

CPU 31xC and CPU 31x, Technical data

6-45

Manual, Edition 08/2004, A5E00105475-05