Siemens S7-300 appendix Technical data

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 181
Image 181

Technical data of CPU 31x 7.4 CPU 315-2 DP

Technical data

 

Number of function modules and communication

 

processors you can operate

 

FM

Max. 8

CP (PtP)

Max. 8

CP (LAN)

Max. 10

Time-of-day

 

Real-time clock

Yes (HW clock)

Buffered

Yes

Buffered period

Typically 6 weeks (at an ambient temperature of

 

 

104 °F)

Behavior of the clock on expiration of the

The clock keeps running, continuing at the time-

 

buffered period

of-day it had when power was switched off.

Accuracy

Deviation per day: < 10 s

Operating hours counter

1

Number

0

Value range

2 31 hours

 

 

(if SFC 101 is used)

Granularity

1 hour

Retentive

yes; must be manually restarted after every

 

 

restart

Clock synchronization

Yes

In the PLC

Master

On MPI

Master/slave

S7 signaling functions

 

Number of stations that can log in for signaling

16

functions (e.g. OS)

(depends on the number of connections

 

 

configured for PG / OP and S7 basic

 

 

communication)

Process diagnostics messages

Yes

Simultaneously enabled interrupt S blocks

40

Testing and commissioning functions

 

Status/control variables

Yes

Variables

Inputs, outputs, memory bits, DBs, timers,

 

 

counters

Number of variables

30

 

Of those as status variable

30

 

Of those as control variable

14

Forcing

 

Variables

Inputs/Outputs

Number of variables

Max. 10

Block status

Yes

Single step

Yes

Breakpoints

2

CPU 31xC and CPU 31x, Technical data

7-15

Manual, Edition 08/2004, A5E00105475-05

Page 181
Image 181
Siemens S7-300 appendix Technical data