Siemens S7-300 appendix Technical data of digital outputs

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 159
Image 159

Technical data of CPU 31xC 6.6 Technical data of the integrated I/O

Technical data

Table 6-13 Technical data of digital outputs

Technical data

 

 

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Module-specific data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Number of outputs

6

16

16

16

Of those are fast outputs

2

4

4

4

 

 

Caution:

 

 

 

 

 

You cannot connect the high-speed outputs of your CPU in parallel.

Cable length

 

 

 

 

Unshielded

Max. 600 m

 

 

 

Shielded

Max. 1000 m

 

 

 

Voltage, currents, potentials

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Rated load voltage L+

24 VDC

 

 

 

Polarity reversal protection

No

 

 

 

Total current of outputs (per group)

 

 

 

 

Horizontal assembly

 

 

 

 

 

up to 104 °F

 

 

 

 

 

Max. 2.0 A

Max. 3,0 A

Max. 3,0 A

Max. 3,0 A

 

up to 60 °C

Max. 1,5 A

Max. 2.0 A

Max. 2.0 A

Max. 2.0 A

Vertical assembly

 

 

 

 

 

up to 104 °F

 

 

 

 

 

Max. 1,5 A

Max. 2.0 A

Max. 2.0 A

Max. 2.0 A

Electrical isolation

 

 

 

 

Between channels and the backplane bus

Yes

 

 

 

Between the channels

No

Yes

Yes

Yes

 

In groups of

8

8

8

Permitted potential difference

 

 

 

 

Between different circuits

75 VDC / 60 VAC

 

 

 

Insulation test voltage

500 VDC

 

 

 

Current consumption

 

 

 

 

with load voltage L+

Max. 50 mA

Max. 100 mA

Max. 100 mA

Max. 100 mA

Status, interrupts, diagnostics

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Status display

green LED per channel

 

 

Interrupts

no interrupts when operated as standard I/O

 

 

 

For using technological functions, please refer to the Technological

 

 

Functions Manual.

 

 

Diagnostics functions

no diagnostics when operated as standard I/O

 

 

 

For using technological functions, please refer to the Technological

 

 

Functions Manual.

 

 

CPU 31xC and CPU 31x, Technical data

6-49

Manual, Edition 08/2004, A5E00105475-05