Technical data of CPU 31xC

 

 

 

 

 

6.4 CPU 313C-2 PtP and CPU 313C-2 DP

 

 

 

 

 

 

Technical data

 

 

 

 

 

 

 

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

DP slave

 

 

 

 

Number of connections

 

8

 

Services

 

 

 

 

PG/OP communication

 

Yes

 

Routing

 

Yes (only if interface is active)

 

Global data communication

 

No

 

S7 basic communication

 

No

 

S7 communication

 

No

 

Direct data exchange

 

Yes

 

Transmission rates

 

Up to 12 Mbps

 

Automatic baud rate search

 

Yes (only if interface is passive)

 

Intermediate memory

 

244 bytes I / 244 bytes O

 

Address areas

 

Max. 32, with max. 32 bytes each

 

DPV1

 

No

 

GSD file

 

The latest GSD file is available at:

 

 

 

 

 

 

http://www.ad.siemens.de/support

 

 

 

 

 

 

in the Product Support area

 

Point-to-point communication

 

 

 

 

Transmission rates

38.4 kbps half duplex

 

 

 

 

 

19.2 kbps full duplex

 

 

 

Cable length

Max. 1200 m

 

 

User program can control the interface

Yes

 

 

The interface can trigger a break or an

Yes (message with break ID)

 

 

 

interrupt in the user program

 

 

 

 

Protocol driver

3964(R); ASCII

 

 

Programming

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

Programming language

LAD/FBD/STL

 

 

 

Available instructions

see the Instruction List

 

 

 

Nesting levels

8

 

 

 

System functions (SFCs)

see the Instruction List

 

 

 

System function blocks (SFBs)

see the Instruction List

 

 

 

User program security

Yes

 

 

 

Integrated I/O

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

Default addresses of the integrated

 

 

 

 

 

Digital inputs

124.0 to 125.7

 

 

 

 

Digital outputs

124.0 to 125.7

 

 

CPU 31xC and CPU 31x, Technical data

6-19

Manual, Edition 08/2004, A5E00105475-05

Page 129
Image 129
Siemens S7-300 appendix Technical data CPU 313C-2 PtP CPU 313C-2 DP DP slave, GSD file, Point-to-point communication