Technical data of CPU 31xC 6.6 Technical data of the integrated I/O

Parameters of standard DO

There are no parameters for standard digital outputs.

Parameters of standard AI

The table below gives you an overview of the parameters for standard analog inputs.

Table 6-9

Parameters of standard AI

 

 

 

 

 

 

 

Parameters

 

Value range

Default

Range of efficiency

Integration time (ms)

2,5/16,6/20

20

Channel

Interference suppression

400/60/50

50

Channel

(Hz)

 

 

 

 

(channel 0 to 3)

 

 

 

Measurement range

Disabled/

+/- 10 V

Channel

(channel 0 to 3)

+/- 20 mA/

 

 

 

 

0 ... 20 mA/

 

 

 

 

4 ... 20 mA/

 

 

 

 

+/- 10 V/

 

 

 

 

0 ... 10 V

 

 

Type of measurement

Disabled/

U voltage

Channel

(channel 0 to 3)

V voltage/

 

 

 

 

I current

 

 

Unit of measurement

Celsius/Fahrenheit/

Celsius

Channel

(channel 4)

 

Kelvin

 

 

Measurement range

Disabled/

600 Ω

Channel

(Pt 100 input; channel 4)

Pt 100/600 Ω

 

 

Type of measurement

Disabled/

Resistance

Channel

(Pt 100 input; channel 4)

resistor/

 

 

 

 

thermocouple

 

 

Reference

See also Chapter 4.3 in the Module Data Reference Manual.

CPU 31xC and CPU 31x, Technical data

6-41

Manual, Edition 08/2004, A5E00105475-05

Page 151