Technical data of CPU 31xC 6.3 CPU 313C

Technical data

Integrated I/O

Default addresses of the integrated

Digital inputs

124.0 to 126.7

Digital outputs

124.0 to 125.7

Analog inputs

752 to 761

Analog outputs

752 to 755

 

 

Integrated functions

 

Counters

3 channels (see the Manual Technological

 

 

Functions)

Frequency counters

3 channels, max. 30 kHz (see the Manual

 

 

Technological Functions)

Pulse outputs

3 channels for pulse width modulation, max. 2.5

 

 

kHz (see the Manual Technological Functions)

Controlled positioning

No

Integrated "Controlling" SFB

PID controller (see the Manual Technological

 

 

Functions)

Dimensions

 

Mounting dimensions W x H x D (mm)

120 x 125 x 130

Weight

 

660 g

Voltages and currents

 

Power supply (rated value)

24 VDC

Permitted range

20.4 V to 28.8 V

Current consumption (no-load operation)

Typically 150 mA

Inrush current

Typically 11 A

Power consumption (nominal value)

700 mA

I2t

 

0.7 A2s

External fusing of power supply lines

LS switch Type C min. 2 A,

(recommended)

LS switch Type B min. 4 A,

Power loss

Typically 14 W

Reference

In Chapter Specifications of the integrated I/O you can find

the specifications of integrated I/O under Digital inputs of CPUs 31xC, Digital outputs of CPUs 31xC, Analog inputs of CPUs 31xC and Analog outputs of CPUs 31xC.

the block diagrams of the integrated I/Os under Arrangement and usage of integrated I/Os.

CPU 31xC and CPU 31x, Technical data

6-13

Manual, Edition 08/2004, A5E00105475-05

Page 123
Image 123
Siemens S7-300 appendix Technical data Integrated I/O, KHz see the Manual Technological Functions