Siemens S7-300 appendix Routing Interface X1 configured as Yes

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 203
Image 203

Technical data of CPU 31x 7.7 CPU 317-2 PN/DP

Technical data

Routing

 

 

Interface X1 configured as

 

Yes

 

MPI

 

Max. 10

 

DP master

 

Max. 24

 

DP slave (active)

 

Max. 14

Interface X2 configured as

 

 

 

PROFINET

 

Max. 24

 

 

 

 

CBA (at 50 % communication load)

 

Maximum data length for arrays and

 

 

 

structures between two partners

 

 

 

Acyclic PROFINET interconnections

 

1400 bytes

 

Cyclic PROFINET interconnections

 

 

 

450 bytes

 

Local interconnections

 

 

 

Slave-dependent

 

 

 

 

Number of coupled PROFIBUS devices

 

16

Total of all master/slave connections

 

1000

Number of device-internal and PROFIBUS

 

500

 

interconnections

 

 

Number of remote interconnecting partners

 

32

Remote interconnections with acyclical transmission

Scan rate: Minimum scan interval

 

500 ms

Number of incoming interconnections

 

100

Number of outgoing interconnections

 

100

Remote interconnections with cyclical transmission

 

Scan rate: Minimum scan interval

 

10 ms

Number of incoming interconnections

 

200

Number of outgoing interconnections

 

200

HMI interconnections via PROFINET (acyclic)

 

HMI interconnections

 

500 ms

Number of HMI variables

 

200

Sum of all interconnections

 

4000 bytes input/4000 bytes output

Interfaces

 

 

1st interface

 

 

Type of interface

 

Integrated RS485 interface

Physics

 

RS 485

electrically isolated

 

Yes

Interface power supply

 

max. 200 mA

(15 to 30 VDC)

 

 

Functionality

 

 

MPI

 

Yes

PROFIBUS DP

 

Yes

Point-to-point communication

 

No

PROFINET

 

No

CPU 31xC and CPU 31x, Technical data

7-37

Manual, Edition 08/2004, A5E00105475-05

Page 203
Image 203
Siemens S7-300 appendix Routing Interface X1 configured as Yes