Siemens S7-300 Analog inputs, Technical data Module-specific data, Voltage, currents, potentials

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 161
Image 161

Technical data of CPU 31xC 6.6 Technical data of the integrated I/O

6.6.8Analog inputs

Introduction

This chapter contains the specifications for analog outputs of CPUs 31xC. The table includes the following CPUs:

CPU 313C

CPU 314C-2 DP

CPU 314C-2 PtP

Technical data

Table 6-14 Technical data of analog inputs

Technical data

Module-specific data

Number of inputs

4 channels with current/voltage input

 

 

1 channel with resistance input

Cable length

 

Shielded

Max. 100 m

Voltage, currents, potentials

 

Resistance input

 

No-load voltage

Typically 2.5 V

Measurement current

Typically 1.8 mA to 3.3 mA

Electrical isolation

 

Between channels and the backplane bus

Yes

Between the channels

No

Permitted potential difference

 

Between inputs (AIC) and MANA (UCM)

8.0 VDC

between MANA and Minternal (UISO)

75 VDC / 60 VAC

Insulation test voltage

600 VDC

Analog value generation

 

Measurement principle

Actual value encoding (successive

 

 

approximation)

Integration time/conversion time/resolution (per channel)

 

Configurable

Yes

Integration time in ms

2,5 / 16,6 / 20

Permitted input frequency

Max. 400 Hz

Resolution (including overdrive)

11 bits + signed bit

Suppression of interference frequency f1

400 / 60 / 50 Hz

CPU 31xC and CPU 31x, Technical data

6-51

Manual, Edition 08/2004, A5E00105475-05