Technical data of CPU 31xC

 

 

 

 

 

6.4 CPU 313C-2 PtP and CPU 313C-2 DP

 

 

 

 

 

 

Technical data

 

 

 

 

 

 

 

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

Communication functions

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

PG/OP communication

Yes

 

 

 

Global data communication

Yes

 

 

 

Number of GD circuits

4

 

 

 

Number of GD packets

Max. 4

 

 

 

 

Sending stations

Max. 4

 

 

 

 

Receiving stations

Max. 4

 

 

 

Length of GD packets

max. 22 bytes

 

 

 

 

Consistent data

22 bytes

 

 

 

S7 basic communication

Yes (server)

 

 

 

User data per request

max. 76 bytes

 

 

 

 

Consistent data

76 bytes (for X_SEND or X_RCV)

 

 

 

 

64 bytes (for X_PUT or X_GET as the server)

 

S7 communication

 

 

 

 

As server

Yes

 

 

 

as client

Yes (via CP and loadable FBs)

 

 

 

User data per request

max. 180 bytes (with PUT/GET)

 

 

 

 

Consistent data

64 bytes

 

 

 

S5-compatible communication

Yes (via CP and loadable FCs)

 

 

 

Number of connections

Max. 8

 

 

 

can be used for

 

 

 

 

PG communication

Max. 7

 

 

 

 

Reserved (default)

1

 

 

 

 

Configurable

from 1 to 7

 

 

 

OP communication

Max. 7

 

 

 

 

Reserved (default)

1

 

 

 

 

Configurable

from 1 to 7

 

 

 

S7-based communication

Max. 4

 

 

 

 

Reserved (default)

4

 

 

 

 

Configurable

from 0 to 4

 

 

 

Routing

No

 

Max. 4

 

Interfaces

CPU 313C-2 PtP

 

CPU 313C-2 DP

 

1st interface

 

 

 

 

Type of interface

Integrated RS485 interface

 

 

 

Physics

RS 485

 

 

 

electrically isolated

No

 

 

 

Interface power supply (15 to 30 VDC)

Max. 200 mA

 

 

 

Functionality

 

 

 

 

MPI

Yes

 

 

 

PROFIBUS DP

No

 

 

 

Point-to-point communication

No

 

 

CPU 31xC and CPU 31x, Technical data

6-17

Manual, Edition 08/2004, A5E00105475-05

Page 127
Image 127
Siemens S7-300 appendix Interfaces CPU 313C-2 PtP CPU 313C-2 DP 1st interface, Functionality