Siemens S7-300 appendix Technical data

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 186
Image 186

Technical data of CPU 31x 7.5 CPU 315-2 PN/DP

Technical data

IEC Timers

Yes

Type

SFB

Number

Unlimited

 

 

(limited only by RAM size)

Data areas and their retentivity

 

Flag bits

2048 bytes

Retentive memory

Configurable

Default retentivity

From MB0 to MB15

Clock flag bits

8 (1 byte per flag bit)

Data blocks

 

Number

1023

 

 

(DB 1 to DB 1023)

Length

16 KB

Non-Retain support (configured retention)

Yes

Local data per priority class

Max. 1024 bytes per run level / 510 bytes per

 

 

block

Blocks

 

Total

1024 (DBs, FCs, FBs)

 

 

The maximum number of blocks that can be

 

 

loaded may be reduced if you are using another

 

 

MMC.

OBs

See the Instruction List

Length

16 KB

Nesting depth

 

Per priority class

8

additional within an error OB

4

FBs

See the Instruction List

Number

2048

 

 

(FB 0 to FB 2047)

Length

16 KB

FCs

See the Instruction List

Number

2048

 

 

(FC 0 to FC 2047)

Length

16 KB

Address areas (I/O)

 

Total I/O address area

max. 2048 bytes/2048 bytes

 

 

(can be freely addressed)

Distributed

max. 2000 bytes

I/O process image

128/128

Digital channels

16384/16384

of those local

Max. 1024

Analog channels

1024/1024

of those local

Max. 256

7-20

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 186
Image 186
Siemens S7-300 appendix Technical data