Siemens S7-300 appendix CPU 31xC and CPU 31x, Technical data

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 160
Image 160

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

Technical data

 

 

 

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Data for the selection of an actuator for

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

standard DI

 

 

 

 

Output voltage

 

 

 

 

For signal "1"

Min. L+ (-0.8 V)

 

 

 

Output current

 

 

 

 

For signal "1"

0,5 A

 

 

 

 

Rated value

5 mA to 600 mA

 

 

 

 

Permitted range

 

 

 

 

For signal "0" (residual current)

Max. 0.5 mA

 

 

 

Load impedance range

48 Ω to 4 kΩ

 

 

 

Lamp load

Max. 5 W

 

 

 

Parallel connection of 2 outputs

 

 

 

 

for redundant load control

Possible

 

 

 

for performance increase

Not possible

 

 

 

Controlling of digital inputs

Possible

 

 

 

Switching frequency

 

 

 

 

under resistive load

Max. 100 Hz

 

 

 

For inductive load to IEC 947-5, DC13

Max. 0.5 Hz

 

 

 

under lamp load

Max. 100 Hz

 

 

 

fast outputs under resistive load

Max. 2.5 kHz

 

 

 

Inductive breaking voltage limited internally to

Typically (L+) - 48 V

 

 

Short-circuit protection of the output

Yes, electronic

 

 

 

Response threshold

Typically 1 A

 

 

 

6-50

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 160
Image 160
Siemens S7-300 appendix CPU 31xC and CPU 31x, Technical data