Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

Technical data

 

 

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Data for the selection of an encoder for

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

standard DI

 

 

 

 

Input voltage

 

 

 

 

Rated value

24 VDC

 

 

 

For signal "1"

15 V to 30 V

 

 

 

For signal "0"

-3 V to 5 V

 

 

 

Input current

 

 

 

 

For signal "1"

Typically 9 mA

 

 

 

Delay of standard inputs

 

 

 

 

Configurable

Yes (0.1 / 0.5 / 3 / 15 ms)

 

 

 

 

You can reconfigure the input delay of the standard inputs during program

 

 

runtime. Please note that your newly set filter time may only take effect

 

 

after the previously set filter time has expired.

 

Rated value

3 ms

 

 

 

For using technological functions:

48 μs

16 μs

16 μs

8 μs

"Minimum pulse width/ minimum pause

 

 

 

 

between pulses at maximum counting

 

 

 

 

frequency"

 

 

 

 

Input characteristics curve

to IEC 1131, type 1

 

 

Connection of 2­wire BEROs

Possible

 

 

 

Permitted quiescent current

Max. 1,5 mA

 

 

 

6.6.7Digital outputs

Introduction

This chapter contains the specifications for the digital outputs of CPUs 31xC.

The table includes the following CPUs:

under CPU 313C-2, the CPU 313C-2 DP and CPU 313C-2 PtP

under CPU 314C-2, the CPU 314C-2 DP and CPU 314C-2 PtP

Fast digital outputs

Technological functions use fast digital outputs.

6-48

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 158
Image 158
Siemens S7-300 appendix Digital outputs, Fast digital outputs, Technological functions use fast digital outputs