Technical data of CPU 31x 7.5 CPU 315-2 PN/DP

Technical data

Assembly

Racks

Max. 4

Modules per rack

8

Number of DP masters

 

Integrated

1

via CP

2

Number of function modules and communication processors you can operate

FM

Max. 8

CP (PtP)

Max. 8

CP (LAN)

Max. 10

Time-of-day

 

Real-time clock

Yes (hardware clock)

Factory setting

DT#1994-01-01-00:00:00

Buffered

Yes

Buffered period

Typically 6 weeks (at an ambient temperature of

 

 

104 °F)

Behavior of the clock on expiration of the

The clock keeps running, continuing at the time-

 

buffered period

of-day it had when power was switched off.

Behavior of the realtime clock after POWER

The clock continues running after POWER OFF.

 

ON

 

Accuracy

Deviation per day: < 10 s

Operating hours counter

1

Number

0

Value range

2 31 hours

 

 

(if SFC 101 is used)

Granularity

1 hour

Retentive

yes; must be manually restarted after every

 

 

restart

Clock synchronization

Yes

In the PLC

Master/slave

On MPI

Master/slave

S7 signaling functions

 

Number of stations that can be logged on for

16

signaling functions

(depends on the number of connections

 

 

configured for PG / OP and S7 basic

 

 

communication)

Process diagnostics messages

Yes

Simultaneously enabled interrupt S blocks

40

Testing and commissioning functions

 

Status/control variables

Yes

Variables

Inputs, outputs, memory bits, DBs, timers,

 

 

counters

CPU 31xC and CPU 31x, Technical data

7-21

Manual, Edition 08/2004, A5E00105475-05

Page 187
Image 187
Siemens S7-300 appendix Technical data Assembly