Technical data of CPU 31xC

6.5 CPU 314C-2 PtP and CPU 314C-2 DP

Technical data

 

 

 

CPU 314C-2 PtP

CPU 314C-2 DP

DP slave

 

 

Number of connections

12

Services

 

 

PG/OP communication

Yes

Routing

Yes (only if interface is active)

Global data communication

No

S7 basic communication

No

S7 communication

No

Direct data exchange

Yes

Transmission rates

Up to 12 Mbps

Intermediate memory

244 bytes I / 244 bytes O

Automatic baud rate search

Yes (only if interface is passive)

Address areas

 

Max. 32, with max. 32 bytes each

DPV1

No

GSD file

The latest GSD file is available at:

 

 

 

 

http://www.ad.siemens.de/support

 

 

 

 

in the Product Support area

Point-to-point communication

 

 

Transmission rates

38.4 kbps half duplex

 

 

 

19.2 kbps full duplex

 

Cable length

Max. 1200 m

User program can control the

Yes

 

interface

 

 

The interface can trigger a break or

Yes (message with break ID)

 

an interrupt in the user program

 

 

Protocol driver

3964 (R); ASCII and RK512

Programming

CPU 314C-2 PtP

CPU 314C-2 DP

Programming language

LAD/FBD/STL

 

Available instructions

see the Instruction List

 

Nesting levels

8

 

System functions (SFCs)

see the Instruction List

 

System function blocks (SFBs)

see the Instruction List

 

User program security

Yes

 

Integrated I/O

CPU 314C-2 PtP

CPU 314C-2 DP

Default addresses of the integrated

 

 

 

Digital inputs

124.0 to 126.7

 

 

Digital outputs

124.0 to 125.7

 

 

Analog inputs

752 to 761

 

 

Analog outputs

752 to 755

 

 

 

 

 

6-26

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 136
Image 136
Siemens S7-300 appendix Technical data CPU 314C-2 PtP CPU 314C-2 DP DP slave, Programming CPU 314C-2 PtP CPU 314C-2 DP