Technical data of CPU 31x 7.6 CPU 317-2 DP

Technical data

Number of connections

32

can be used for

 

PG communication

Max. 31

 

Reserved (default)

1

 

Configurable

1 to 31

OP communication

Max. 31

 

Reserved (default)

1

 

Configurable

1 to 31

S7-based communication

Max. 30

 

Reserved (default)

0

 

Configurable

0 to 30

Routing

Yes (max. 8)

Interfaces

 

1st interface

 

Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

Yes

Interface power supply

max. 200 mA

(15 to 30 VDC)

 

Functionality

 

MPI

Yes

PROFIBUS DP

Yes

Point-to-point communication

No

MPI

 

 

Services

 

PG/OP communication

Yes

Routing

Yes

Global data communication

Yes

S7 basic communication

Yes

S7 communication

 

 

As server

Yes

 

As client

No (but via CP and loadable FBs)

Transmission rates

Max. 12 Mbps

DP master

 

Services

 

PG/OP communication

Yes

Routing

Yes

Global data communication

No

S7 basic communication

No

S7 communication

No

Constant bus cycle time

Yes

SYNC/FREEZE

Yes

DPV1

Yes

7-30