Communication

3.2 Communication services

The following table provides you with an overview of the system and standard functions for SIMATIC, whose functionality must be implemented by other functions when converting from PROFIBUS DP to PROFINET IO.

Table 3-7

System and Standard Functions in PROFIBUS DP that must be Implemented with

 

Different Functions in PROFINET IO

 

 

 

 

 

Blocks

 

PROFINET IO

PROFIBUS DP

SFC55 (write dynamic

No

Yes

parameters)

 

(implement with SFB53)

 

SFC56 (write predefined

No

Yes

parameters)

 

(implement with SFB81 and

 

 

 

SFB53)

 

SFC57 (assign parameters to

No

Yes

module)

 

(implement with SFB81 and

 

 

 

SFB53)

 

You cannot use the following SIMATIC system and standard functions with PROFINET IO:

SFC7 (trigger hardware interrupt on DP master)

SFC11 (synchronize groups of DP slaves)

SFC12 (deactivate and activate DP slaves)

SFC72 (read data from a communication partner within local S7 station)

SFC73 (write data to a communication partner within local S7 station)

SFC74 (abort an existing connection to a communication partner within local S7 station)

Comparison of the Organization Blocks of PROFINET IO and PROFIBUS DP

Here, there are changes in OBs 83 and 86 as shown in the table below.

Table 3-8

OBs in PROFINET IO and PROFIBUS DP

 

 

 

 

 

Blocks

 

PROFINET IO

PROFIBUS DP

OB83 (removing and inserting

Also possible with an S7-300,

With an S7-300 not possible

modules and submodules

new error information

Removing and inserting during

during operation)

 

operation is reported by slaves

 

 

 

added using a GSD file by

 

 

 

means of a diagnostic interrupt;

 

 

 

in other words OB82.

 

 

 

With S7 slaves, OB86 is called

 

 

 

due to the station failure.

OB86 (rack failure)

New error information

Unchanged

Detailed Information

For detailed descriptions of the individual blocks, refer to the manual System Software for S7-300/400 System and Standard Functions.

3-22

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 50
Image 50