Technical data of CPU 31xC 6.6 Technical data of the integrated I/O

Technical data

Table 6-12 Technical data of digital inputs

Technical data

 

 

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Module-specific data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Number of inputs

10

24

16

24

Number of these inputs which can be used

8

12

12

16

 

for technological functions

 

 

 

 

Cable length

 

 

 

 

Unshielded

For standard DI: Max. 600 m

 

 

 

 

For technological functions: No

 

 

Shielded

For standard DI: Max. 1000 m

 

 

 

 

For technological function at max. counting frequency

 

 

 

100 m

100 m

100 m

50 m

Voltage, currents, potentials

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Rated load voltage L+

24 VDC

 

 

 

Polarity reversal protection

Yes

 

 

 

Number of inputs which can be controlled

 

 

 

 

simultaneously

 

 

 

 

Horizontal assembly

 

 

 

 

 

up to 104 °F

10

24

16

24

 

up to 60 °C

5

12

8

12

Vertical assembly

 

 

 

 

 

up to 104 °F

5

12

8

12

Electrical isolation

 

 

 

 

Between channels and the backplane bus

Yes

 

 

 

Between the channels

No

 

 

 

Permitted potential difference

 

 

 

 

Between different circuits

75 VDC / 60 VAC

 

 

 

Insulation test voltage

500 VDC

 

 

 

Current consumption

 

 

 

 

On load voltage L+ (no-load)

Max. 70 mA

Max. 70 mA

Max. 70 mA

Status, interrupts, diagnostics

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Status display

green LED per channel

 

 

Interrupts

Yes, if the corresponding channel is configured as interrupt input

 

 

For using technological functions, please refer to the Technological

 

 

Functions Manual.

 

 

Diagnostics functions

no diagnostics when operated as standard I/O

 

 

 

For using technological functions, please refer to the Technological

 

 

Functions Manual.

 

 

CPU 31xC and CPU 31x, Technical data