Siemens S7-300 appendix GSD file

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 198
Image 198

Technical data of CPU 31x 7.6 CPU 317-2 DP

Technical data

DP slave

(except for DP slave at both interfaces)

Services

 

PG/OP communication

Yes

Routing

Yes (only if interface is active)

Global data communication

No

S7 basic communication

No

S7 communication

No

Direct data exchange

Yes

Transmission rates

Up to 12 Mbps

Automatic baud rate search

Yes (only if interface is passive)

Intermediate memory

244 bytes I / 244 bytes O

Address areas

max. 32 with max. 32 bytes each

DPV1

No

GSD file

The latest GSD file is available at:

 

 

http://www.ad.siemens.de/support

 

 

in the Product Support area

Programming

 

Programming language

LAD/FBD/STL

Available instructions

See the Instruction List

Nesting levels

8

System functions (SFCs)

See the Instruction List

System function blocks (SFBs)

See the Instruction List

User program security

Yes

Dimensions

 

Mounting dimensions W x H x D (mm)

80 x 125 x 130

Weight

460 g

Voltages and currents

 

Power supply (rated value)

24 VDC

Permitted range

20.4 V to 28.8 V

Current consumption (no-load operation)

Typically 100 mA

Inrush current

Typically 2.5 A

I2t

 

1 A2s

External fusing of power supply lines

min. 2 A

(recommended)

 

Power loss

Typically 4 W

7-32

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 198
Image 198
Siemens S7-300 appendix GSD file