Siemens S7-300 appendix Analog value generation, Actuator selection data

Models: S7-300

1 244
Download 244 pages 25.52 Kb
Page 164
Image 164

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

Technical data

Permitted potential difference

 

between MANA and Minternal (UISO)

75 VDC / 60 VAC

Insulation test voltage

600 VDC

Analog value generation

 

Resolution (including overdrive)

11 bits + signed bit

Conversion time (per channel)

1 ms

Settling time

 

with resistive load

0,6 ms

With capacitive load

1,0 ms

With inductive load

0.5 ms

Interference suppression, error limits

 

Crosstalk between the outputs

> 60 dB

Operational error limits (across the temperature range, in relation to output

 

range)

 

 

Voltage/current

± 1 %

Basic error limit (operational limit at 25 °C, in relation to output range)

 

Voltage/current

± 0,7 %

Temperature error (in relation to output range)

± 0.01 %/K

Linearity error (in relation to output range)

± 0,15 %

Repeat accuracy (in transient state at 25 °C, in relation to output range)

± 0,06 %

Output ripple; bandwidth 0 to 50 kHz (in relation to output range)

± 0,1 %

Status, interrupts, diagnostics

 

Interrupts

no interrupts when operated as standard

 

 

 

I/O

 

 

 

For using technological functions, please

 

 

 

refer to the Technological Functions

 

 

 

Manual.

Diagnostics functions

no diagnostics when operated as

 

 

 

standard I/O

 

 

 

For using technological functions, please

 

 

 

refer to the Technological Functions

 

 

 

Manual.

Actuator selection data

 

Output range (rated values)

 

Voltage

± 10 V

 

 

 

0 V to 10 V

Current

± 20 mA

 

 

 

0 mA to 20 mA

 

 

 

4 mA to 20 mA

Load resistance (within output rating)

 

For voltage outputs

min. 1 kΩ

 

Capacitive load

max. 0.1 μF

For current outputs

max. 300 Ω

 

Inductive load

0.1 mH

6-54

CPU 31xC and CPU 31x, Technical data

Manual, Edition 08/2004, A5E00105475-05

Page 164
Image 164
Siemens S7-300 appendix Analog value generation, Actuator selection data