Cleveland Range inverter manual MODBUS-RTUCommunication, Negative Acknowledge Response, Error Code

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 86
Image 86
Error Code

Chapter 5 - MODBUS-RTU Communication

Negative Acknowledge Response

NAK

Drive No.

CMD

Error Code

SUM

EOT

15h

“01” ~ “1F”

“X”

“**”

“XX”

04h

1 byte

2 bytes

1 byte

2 bytes

2 bytes

1 byte

Total byte = 9 bytes

Action Request for Monitor Registration: Request for read of address registered by monitor registration.

ENQ

 

 

 

Drive No.

 

 

CMD

 

SUM

 

EOT

 

05h

 

 

“01” ~ “1F”

 

 

“Y”

 

“XX”

 

04h

 

1 byte

 

 

 

2 bytes

 

 

1 byte

 

2 bytes

 

1 byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total byte = 7 bytes

 

 

 

 

 

 

 

 

 

 

 

 

Acknowledge Response

 

 

 

 

 

 

 

 

 

ACK

 

 

Drive

 

CMD

 

 

Data

 

SUM

EOT

 

06h

 

 

“01” ~

 

 

“Y”

 

 

“XXXX

 

“XX”

04h

 

1 byte

 

2 bytes

 

1 byte

 

n * 4

 

2 bytes

1 byte

 

Total byte= 7 + n * 4 = max. 39 bytes

 

 

 

 

 

Negative Acknowledge Response

 

 

 

 

 

NAK

 

 

Drive

 

CMD

 

 

Error

 

SUM

EOT

 

15h

 

 

“01” ~

 

 

“Y”

 

 

“**”

 

“XX”

04h

 

1 byte

 

2 bytes

 

1 byte

 

2 bytes

 

2 bytes

1 byte

 

Total byte = 9 bytes

 

 

 

 

 

 

 

 

 

 

 

 

Error Code

 

 

 

 

 

 

 

 

 

 

 

 

Error Code

 

 

 

 

 

 

 

Description

 

 

SE

 

 

 

Sum Error

 

 

 

 

 

 

 

 

 

FE

 

 

 

Frame Error

 

 

 

 

 

 

 

 

 

FC

 

 

 

Frame Error (Command): Not in use

 

 

FS

 

 

 

Frame Error (Size)

 

 

 

 

 

EE

 

 

 

Parameter EEP Access Error

 

 

80

Page 86