Chapter 4 - Parameter Description [DRV]

 

 

 

 

 

Chapter 4 - Parameter Description [DRV]

 

 

 

 

 

 

 

 

DRV-03: Drive Mode (Run/stop Method)

DRV-04: Frequency Mode (Frequency Setting

 

 

 

 

 

Method)

 

 

 

 

 

 

 

Select the source of Run/Stop command.

 

 

 

 

 

 

 

 

 

 

Select the source of frequency setting.

Setting Range

 

Description

 

 

 

 

 

 

 

 

Select

Display

 

 

 

 

 

Setting Range

Description

 

 

 

 

 

 

 

Keypad

0

Run/stop is controlled by Keypad.

 

 

 

 

 

 

Select

Display

 

 

 

 

 

 

 

Control Terminals FX, RX and CM

 

 

 

 

 

 

Fx/Rx-1

1

 

 

 

 

Frequency is set at DRV-00. The

control Run/Stop. (Method 1)

 

 

 

 

frequency is changed by pressing

 

 

 

 

 

 

 

Fx/Rx-2

2

Control Terminals FX, RX and CM

 

 

Keypad-1

0

[FUNC] key and entered by pressing

control Run/Stop. (Method 2)

 

 

[FUNC] key. The inverter does not output

 

 

 

 

 

 

 

MODBUS-

 

Run/stop is controlled by Serial

 

 

 

 

the changed frequency until the [FUNC]

3

Communication (MODBUS-RTU)

 

 

 

 

key is pressed.

RTU

 

 

 

 

 

Refer to Chapter 5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency is set at DRV-00. Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[FUNC] key and then by pressing the

Output Frequency

 

 

 

 

 

 

 

Keypad-2

1

[▲], [▼] key, the inverter immediately

 

 

 

 

 

 

 

outputs the changed frequency. Pressing

 

 

 

 

 

 

 

 

 

 

 

 

the [FUNC] key saves the changed

Forward

 

 

 

 

 

 

 

 

 

 

frequency.

 

 

 

 

 

 

 

 

 

 

Input the frequency reference (0-10V) to

 

 

 

 

 

 

 

Time

 

 

V1

2

the “V1” control terminal. Refer to the I/O-

 

 

 

 

 

 

 

 

 

Reverse

 

 

 

 

 

 

 

 

 

 

01 to I/O-05 for scaling the signal.

 

 

 

 

 

 

 

 

 

 

Input the frequency reference (4~20mA)

 

 

 

 

 

 

 

 

 

 

I

3

to the “I” control terminal. Refer to the

 

 

 

 

 

 

 

 

 

 

 

 

I/O-06 to I/O-10 for scaling the signal.

 

 

 

 

 

 

Forward Run

 

 

 

 

Input the frequency reference (0~10V,

 

 

 

 

 

 

 

 

 

 

FX-CM

 

ON

 

 

 

 

 

 

 

V1+I

4

4~20mA) to the “V1”,“I” control terminals.

 

 

 

 

 

 

Reverse Run

 

 

 

 

The ‘V1’ signal overrides the ‘I’ signal.

 

 

 

 

 

 

 

 

 

 

RX-CM

 

 

 

ON

 

 

 

MODBUS-

 

Frequency is set by Serial

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Communication (MODBUS-RTU)

 

 

 

 

 

 

 

 

 

 

RTU

 

 

 

 

 

 

 

 

 

 

 

Refer to Chapter 5.

 

 

[Drive Mode: ‘Fx/Rx-1’]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Frequency

 

 

 

 

 

 

Related Functions: I/O-01 to I/O-10 [Reference Inputs]

 

 

 

 

 

 

 

 

I/O-01 to I/O-10: Scaling analog input signals (V1 and I) for

 

 

 

 

 

 

 

 

 

 

 

frequency reference.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forward

 

 

 

 

 

 

 

Time

Output Frequency

 

 

 

 

 

 

 

Reverse

 

 

Freq. Max

 

 

 

 

 

 

 

FX-CM

ON

Run/Stop

 

 

Reference Freq. Range

RX-CM

ON

Direction

0V

10V

Analog Signal

 

 

 

Input (V1)

 

[Drive Mode: ‘Fx/Rx-2’]

 

 

[Freq Mode: ‘V1’]

35

Page 41
Image 41
Cleveland Range inverter manual Parameter Description DRV, DRV-03 Drive Mode Run/stop Method