Cleveland Range inverter Parameter Code List, MODBUS-RTUCommunication, Common, Description, Unit

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 87
Image 87
5.7 Parameter Code List

Chapter 5 - MODBUS-RTU Communication

5.7 Parameter Code List

< Common >

 

Parameter

 

 

Description

 

 

Unit

 

 

Read/Write

 

 

Data value (HEX)

 

 

Note

 

 

address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

 

Inverter model

 

-

 

 

R

 

7: SV-ACtionMaster

 

 

 

 

 

0001

 

 

Inverter capacity

 

-

 

 

R

 

 

0: 0.5Hp, 1: 1Hp, 2: 2Hp

 

 

 

 

 

 

 

 

 

 

 

 

3: 3Hp, 4:5Hp, 5: 5.4Hp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0002

 

 

Inverter input voltage

 

-

 

 

R

 

0: 220V class, 1:440V class

 

 

 

 

 

0003

 

Version

 

-

 

 

R

 

 

313043: Version 1.0C

 

 

 

 

 

 

 

 

 

 

 

353043: Version 5.0C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0004

 

Parameter write enable

 

-

 

 

R/W

 

 

0: Write disable (default)

 

 

 

 

 

 

 

 

 

 

 

1: Write enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0005

 

 

Reference frequency

 

 

0.01 Hz

 

 

R/W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 0: Stop (R/W)

 

 

 

 

 

0006

 

Operation reference

 

-

 

 

R/W

 

 

Bit 1: Forward (R/W)

 

 

 

 

 

 

 

 

 

 

 

Bit 2: Reverse (R/W)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 3: Fault reset (W)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4: Emergency stop (W)

 

 

 

 

 

0007

 

 

Accel time

 

 

0.1 sec

 

 

R/W

 

 

 

 

 

 

 

 

0008

 

 

Decel time

 

 

0.1 sec

 

 

R/W

 

 

 

 

 

 

 

 

0009

 

Output current

 

 

0.1 A

 

 

R

 

 

 

 

 

 

 

 

000A

 

 

Output frequency

 

 

0.01 Hz

 

 

R

 

 

 

 

 

 

 

 

000B

 

 

Output voltage

 

 

1 V

 

 

R

 

 

 

 

 

 

 

 

000C

 

 

DC Link voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

000D

 

 

Output power

 

 

 

 

 

 

 

 

 

 

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 0: Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1: Forward

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2: Reverse

 

 

 

 

 

000E

 

 

Operating status

 

-

 

 

R

 

 

Bit 3: Fault (Trip)

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4: Accelerating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 5: Decelerating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 6: Speed reached

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 7: DC Braking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 0: OC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1: OV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2: EXT

 

 

 

 

 

000F

 

 

Trip info

 

-

 

 

R

 

 

Bit 3: BX

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4: LV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 5: Fuse Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 6: GF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 7: OH

 

 

 

 

 

0010

 

 

Input terminal info

 

-

 

 

R

 

 

Bit 0: FX

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1: RX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

81

Page 87
Image 87
Cleveland Range inverter manual Parameter Code List, MODBUS-RTUCommunication, Common, Description, Unit, Data value HEX