Chapter 6 - Troubleshooting & Maintenance

Inspection Location

 

Inspection Item

 

 

 

 

 

Period

 

 

 

 

 

 

 

 

 

 

 

 

Inspection

 

Daily

 

year1

year2

 

Inspection Method

 

 

Criterion

 

 

Measuring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instrument

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there any abnormal oscillation

Ο

 

 

 

 

Turn OFF the power and turn

 

 

Must rotate

 

 

 

 

Cooling System

Cooling

 

or noise?

 

 

Ο

 

 

the fan by hand.

 

 

smoothly.

 

 

 

 

 

Is the connection area loose?

 

 

 

 

 

Tighten the connections.

 

 

No fault

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the displayed value correct?

Ο

 

Ο

 

 

Check the meter reading at

 

 

Check the

 

 

Voltmeter/

Display

 

Meter

 

 

 

 

 

 

 

 

the exterior of the panel

 

 

specified and

 

 

Ammeter etc.

 

 

 

 

 

 

 

 

 

 

 

 

management

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

values.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are there any abnormal vibrations

Ο

 

 

 

 

Auditory, sensory, visual

 

 

No fault

 

 

 

 

 

 

All

 

or noise?

Ο

 

 

 

 

check.

 

 

 

 

 

 

 

Motor

 

 

Is there any unusual odor?

 

 

 

 

 

Check for overheat and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Insulation

 

Megger check (between the

 

 

 

Ο

Undo the U, V and W

 

 

Over 5MΩ

 

 

500V class

 

 

output terminals and the ground

 

 

 

 

 

connections and tie the motor

 

 

 

 

 

Megger

 

Resistor

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal)

 

 

 

 

 

wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Values in ( ) are for the 400V class inverters.