FU1-54: Overload Warning Level

Chapter 4 - Parameter Description [FU1]

Related Functions: FU2-33 [Rated Motor Current]

FU1-54: Overload Warning Level

FU1-55: Overload Warning Time

The inverter generates an alarm signal when the output current has reached the FU1-54 [Overload Warning Level] for the FU1-55 [Overload Warning Time]. The alarm signal persists for the FU1-55 even if the current has become the level below the FU1-54.

Multi-function output terminal (MO-MG) is used as the alarm signal output. To output the alarm signal, set I/O 44 [Multifunction Output] to ‘OL’.

Note: Inverter is not tripped by this function.

Note: The set value is the percentage of FU2-33 [Rated Motor Current].

Output Current

FU1-54 [OL Level]

FU1-55: Overload Warning Time Time

FU1-54 [OL Level]

MO-MG

 

 

 

 

 

ON

 

Time

 

t1

t1

 

 

 

 

t1: FU1-55 [Overload Warning Time]

[Overload Warning]

Related Functions: FU2-33 [Rated Motor Current] I/O-44 [Multi-function Output]

FU1-56: Overload Trip Selection

FU1-57: Overload Trip Level

FU1-58: Overload Trip Delay Time

Inverter cuts off its output and displays fault message when the output current persists over the FU1-57 [Overload Trip Level] for the time of FU1-58 [Overload Trip Time]. This function protects the inverter and motor from abnormal load conditions.

Note: The set value is the percentage of FU2-33 [Rated Motor Current].

Output Current

FU1-57

 

[OLT Level]

 

 

Time

FU1-57

 

[OLT Level]

 

 

FU1- 58 [OLT Time]

Output Frequency

Overload Trip

 

 

Time

 

[Overload Trip Operation]

47