2.4 Operation

Chapter 2 - Operation

2.4 Operation

2.4.1Operation From Keypad and Control Terminal

When the operation reference signal is given to the control terminal and the frequency setpoint is given by the keypad, set the DRV-03 (drv) to 1 (Fx/Rx-1), and set the DRV-04 (Frq) to 0 (Keypad-1).

The frequency reference signal is set from the control terminal, and the forward, reverse, stop key of the keypad is invalid.

1.Turn the power ON and set the operation and the frequency parameters.

2.Set the DRV-03 (drv) to 1 (Fx/Rx-1), and the DRV-04 (Frq) to 0 (Keypad-1).

3.Turn ON the operation reference signal FX (or RX). Keypad LED (FWD key or REV key) will turn ON.

4.Set the operating frequency with the keypad. Use the FUNC, ▲ (Up), FUNC keys and set the frequency to 50.00Hz. The motor will rotate at 50Hz. The LED (RUN) of the keypad will blink when the inverter is accelerating or decelerating.

5.Turn the operation reference signal FX (or RX) OFF. The LED (FWD of REV) of the keypad will turn OFF.

Note: The user may also operate the inverter by setting the operation reference signal from the Keypad, and setting the frequency reference signal to the control terminal. (Set DRV-03 (drv) to 0 (Keypad), and the DRV-04 (Frq) to 2 (V1)).

2.4.2Operation From Control Terminal

1.Turn the power ON and set the operation and the frequency reference to the control terminal mode.

2.Set the DRV-03 (drv) to 1 (Fx/Rx-1), and the DRV-04 (Frq) to 2 (V1).

3.Set the analog frequency reference by turning the potentiometer (frequency reference) slowly to the right. The keypad will display the output frequency (50.00 Hz).

4.Slowly turning the potentiometer (frequency reference) to the left will decrease the output frequency. The inverter will stop operating and the motor will come to a halt when the frequency reaches 0.00Hz.

5.Turn OFF the operation reference signal FX (or RX).

Note: FU1-20, FU1-21, FU1-25, FU1-36, FU2-54, FU2-83, I/O-05, I/O-10 are set at 50Hz for Standard (EU) types and 60Hz for US types.