Cleveland Range inverter manual Parameter Description FU1, FU1-07 Stop Mode

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 46
Image 46
FU1-07: Stop Mode

Chapter 4 - Parameter Description [FU1]

Output Frequency

 

Time

Acc. Pattern

Dec. Pattern

[Accel/Decel Pattern: ‘Linear’]

Output Frequency

Selects the stopping method for the inverter. Time

Acc. Pattern

Dec. Pattern

[Accel/Decel Pattern: ‘S-Curve’]

Output Frequency

Manual background Time

Acc. Pattern

Dec. Pattern

[Accel/Decel Pattern: ‘U-Curve’]

Setting Range

 

Description

Select

Display

 

Decel

 

0

Inverter stops by the deceleration

 

pattern.

 

 

 

 

 

 

Inverter stops with DC injection

 

 

 

braking. Inverter outputs DC voltage

DC-Brake

 

1

when the frequency reached the DC

 

 

 

injection braking frequency set in FU1-

 

 

 

08 during decelerating.

Free-Run

 

2

Inverter cuts off its output immediately

(Coast to stop)

 

when the stop signal is entered.

 

 

Output Frequency

Manual background Time

Output Voltage

 

 

 

Time

 

 

Stop Command

 

 

 

 

 

 

 

FX-CM

ON

 

Time

 

[Stop Mode: ‘Decel’]

 

 

Output Frequency

 

FU1-08

Manual background Time

Output Voltage

FU1-07: Stop Mode

FU1-10 [DCBr Value]

t1: FU1-09

t2: FU1-11

Manual background Time

Selects the stopping method for the inverter.

t1 t2

Stop Command

 

 

 

 

FX-CM

ON

 

Time

 

 

 

[Stop Mode: ‘DC-Brake’]