Cleveland Range inverter manual Input/Output Group I/O, Parameter List

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 36
Image 36
3.4 Input/Output Group [I/O]

Chapter 3 - Parameter List

 

 

Keypad

 

 

Factory

Adj.

 

Code

Description

Setting Range

Units

During

Page

Display

Default

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

0 (No)

 

 

 

 

 

 

 

1 (All Groups)

 

 

 

 

FU2-93

Initialize Parameters

H 93

2 (DRV)

-

0 (No)

No

60

3 (FU1)

 

 

 

 

 

 

 

 

 

 

4 (FU2)

 

 

 

 

 

 

 

5 (I/O)

 

 

 

 

FU2-94

Parameter Write Protection

H 94

0 to 25518

1

0

Yes

60

FU2-99

Return Code

rt

 

-

-

Yes

60

3.4 Input/Output Group [I/O]

 

 

Keypad

 

 

Factory

Adj.

 

Code

Description

Setting Range

Units

During

Page

Display

Default

 

 

 

 

Run

 

 

 

 

 

 

 

 

I/O-00

Jump to Desired Code #

I 0

1 to 99

1

1

Yes

62

I/O-01

Filtering Time Constant for V1

I 1

0 to 9999 [ms]

1

100 [ms]

Yes

 

Signal Input

 

 

 

 

 

 

 

 

I/O-02

V1 Input Minimum Voltage

I 2

0 to I/O-04

0.01

0.00 [V]

Yes

 

I/O-03

Frequency corresponding to V1

I 3

0 to FU1-20

0.01

0.00 [Hz]

Yes

62

Input Minimum Voltage

 

 

 

 

 

 

 

I/O-04

V1 Input Maximum Voltage

I 4

(I/O-02) to 12.00 [V]

0.01

10.00 [V]

Yes

 

I/O-05

Frequency corresponding to V1

I 5

0.00 to (FU1-20)

0.01

50 / 60 [Hz]

Yes

 

Input Maximum Voltage

 

 

 

 

 

 

 

 

I/O-06

Filtering Time Constant for I Signal

I 6

0 to 9,999 [ms]

1

100 [ms]

Yes

 

Input

 

 

 

 

 

 

 

 

I/O-07

I Input Minimum Current

I 7

0.00 to (I/O-09)

0.01

4.00 [mA]

Yes

 

I/O-08

Frequency corresponding to I Input

I 8

0.00 to (FU1-20)

0.01

0.00 [Hz]

Yes

62

Minimum Current

 

 

 

 

 

 

 

I/O-09

I Input Maximum Current

I 9

(I/O-07) to 24.00[mA]

0.01

20.00 [mA]

Yes

 

I/O-10

Frequency corresponding to I Input

I 10

0.00 to (FU1-20)

0.01

50 /60 [Hz]

Yes

 

Maximum Current

 

 

 

 

 

 

 

 

I/O-11

Criteria for Analog Input Signal Loss

I 11

0 (None)

-

0 (No)

Yes

63

1 (Half of x1)

 

 

 

2 (Below x1)

 

 

 

 

I/O-12

Multi-function Input Terminal ‘P1’

I 12

0 (Speed-L)

-

0 (Speed-L)

No

64

 

Define

 

1 (Speed-M)

 

 

 

 

 

 

 

2 (Speed-H)

 

 

 

 

18This function is used to lock the parameters from being changed. Keypad displays “U 0” when the parameters are unlocked and “L 0” when locked. The lock and unlock code is ‘12’.

30

Page 36
Image 36
Cleveland Range inverter manual Input/Output Group I/O, Parameter List