Chapter 4 - Parameter Description [I/O]

[FDT-1]

When the output frequency reaches the reference frequency (target frequency), MO-MG terminal is

CLOSED.

Output Frequency

 

 

Reference Frequency

 

 

 

I/O-43 / 2

 

 

Time

MO-MG

CLOSED

Time

 

 

 

[MO-MG configured as ‘FDT-1’]

 

[FDT-2]

MO-MG is CLOSED when the reference frequency is in I/O-43 [FDT Bandwidth] centered on I/O-42 [FDT Frequency], and the output frequency reaches I/O-43 centered on I/O-42.

Output Frequency

 

Reference Frequency

 

I/O-42

 

I/O-43 / 2

 

 

 

 

Time

MO-MG

CLOSED

Time

 

 

 

[MO-MG configured as ‘FDT-2’]

 

[FDT-3]

MO-MG is CLOSED when the output frequency reaches the band centered on the FDT frequency. The output is OPENED when the output frequency goes outside the FDT bandwidth centered on the FDT frequency.

Output Frequency

I/O-42

 

 

I/O-43 / 2

 

 

 

 

 

 

Time

MO-MG

ON

ON

Time

 

 

 

 

[MO-MG configured as ‘FDT-3’]

 

[FDT-4]

MO-MG is CLOSED when the output frequency reaches the FDT frequency. The output is OPENED when the output frequency goes below the FDT bandwidth centered on the FDT frequency.

Output Frequency

I/O-42

 

I/O-43 / 2

 

 

 

 

Time

MO-MG

CLOSED

Time

 

[MO-MG configured as ‘FDT-4’]

 

 

[FDT-5]

This is the inverted output of [FDT-4].

Output Frequency

I/O-42

 

I/O-43 / 2

 

 

 

 

Time

MO-MG ON

ON

Time

 

[MO-MG configured as ‘FDT-5’]

 

 