FU1-08: DC Injection Braking Frequency

Chapter 4 - Parameter Description [FU1]

Output Frequency

Output Cutoff

FU1-09: DC Injection Braking On-delay Time Time

Output Voltage

Output Cutoff

 

 

 

Time

 

 

 

 

 

Stop Command

 

 

 

 

FX-CM

ON

 

Time

 

 

 

[Stop Mode: ‘Free-run’]

FU1-09[DC Injection Braking On-delay Time] is the inverter output blocking time before DC injection braking.

FU1-10[DC Injection Braking Voltage] is the DC voltage applied to the motor and is based on FU2- 33 [Rated Current of Motor].

FU1-11[DC Injection Braking Time] is the time the DC current is applied to the motor.

Output Frequency

FU1-08 [DCBr Freq]

FU1-10: DC Injection Braking Voltage Time

Output Voltage

FU1-08: DC Injection Braking Frequency

FU1-09: DC Injection Braking On-delay Time

FU1-10 [DCBr Value]

t1: FU1-09

t2: FU1-11

FU1-11: DC Injection Braking Time Time

FU1-10: DC Injection Braking Voltage

FU1-11: DC Injection Braking Time

This function stops the motor immediately by introducing DC voltage to the motor windings. Selecting ‘DC-Brake’ in FU1-07 activates FU1-08 through FU1-11.

FU1-08[DC Injection Braking Frequency] is the frequency at which the inverter starts to output DC voltage during deceleration.

t1 t2

Stop Command

 

 

 

 

FX-CM

ON

 

Time

 

 

 

[DC Injection Braking Operation]

FU1-12: Starting DC Injection Braking Voltage

FU1-13: Staring DC Injection Braking Time

Inverter holds the starting frequency for Starting DC Injection Braking Time. The inverter outputs DC voltage to the motor for FU1- 13 [Starting DC Injection Braking Time] with the FU1-12 [Starting DC Injection Braking Voltage] before accelerating.

41

Page 47
Image 47