Chapter 4 - Parameter Description [FU1]

Chapter 4 - Parameter Description [FU1]

4.2 Function 1 Group [FU1]

FU1-00: Jump to Desired Code #

Jumping directly to any parameter code can be accomplished by entering the desired code number.

FU1-03: Run Prevention

This function prevents reverse operation of the motor. This function may be used for loads that rotate only in one direction such as fans and pumps.

Setting Range

Description

Select

Display

 

None

0

Forward and reverse run is available.

Forward

1

Forward run is prevented.

Prevention

 

 

Reverse

2

Reverse run is prevented.

Prevention

 

 

FU1-05: Acceleration Pattern

FU1-06: Deceleration Pattern

Different combinations of acceleration and deceleration patterns can be selected according to your application.

Setting Range

Description

Select

Display

 

Linear

0

This is a general pattern for constant

torque applications.

 

 

 

 

This pattern allows the motor to

 

 

accelerate and decelerate smoothly.

 

 

The actual acceleration and

 

 

deceleration time takes longer- about

S-Curve

1

40% than the time set in DRV-01 and

DRV-02.

 

 

 

 

This setting prevents shock during

 

 

acceleration and deceleration, and

 

 

prevents objects from swinging on

 

 

conveyors or other moving equipment.

 

 

This pattern provides more efficient

U-Curve

2

control of acceleration and deceleration

 

 

in typical winding machine applications.

 

 

The inverter makes shorten the

 

 

acceleration time by accelerating with a

 

 

current rate of about 150% of its rated

 

 

current and reduces the deceleration

 

 

time by decelerating with a DC voltage

 

 

rate of 95% of its over-voltage trip level.

Minimum

3

Appropriate application: When the

 

 

maximum capability of the inverter and

 

 

the motor are required.

 

 

Inappropriate application: The current

 

 

limit function may operate for a long

 

 

period of time for loads that have high

 

 

inertia such as fans.

 

 

The inverter accelerates with a current

Optimum

4

rate of about 120% of its rated current

and decelerates with a DC voltage rate

 

 

 

 

of 93% of its over-voltage trip level.

Note: In case of selecting the ‘Minimum’ or ‘Optimum’, the DRV-01 [Accel Time] and DRV-02 [Decel Time] is ignored.

Note: ‘Minimum’ and ‘Optimum’ functions operate normally when the load inertia is less than 10 times compared to the motor inertia. (FU2-37)

Note: ‘Optimum’ is useful when the motor capacity is smaller than the inverter capacity.

Note: ‘Minimum’ and ‘Optimum’ functions are not appropriate for down operation in an elevator application.

39