[V1-Ext]

Chapter 4 - Parameter Description [I/O]

or over voltage trip.

[V1-Ext]

Inverter changes its frequency reference source from keypad to ‘V1’ (analog voltage input) when this terminal is ON.

[Up, Down]

By using the Up and Down function, the drive can accelerate to a steady speed and decelerate down to a desired speed by using only two input terminals.

Output Frequency

Freq.

 

 

 

Max.

 

 

 

 

 

 

Time

P1-CM

ON

 

 

‘Up’

 

Time

P2-CM

 

ON

 

‘Down’

 

Time

 

 

FX-CM

 

ON

Time

 

 

 

 

 

[Up/Down Operation]

 

[3-Wire]

This function is for 3-wire start/stop control. This function is mainly used with a momentary push button to hold the current frequency output during acceleration or deceleration.

FX RX P2 CM

[Wiring for 3-Wire Operation, P2 set to ‘3-Wire’]

Output Frequency

Freq.

 

 

 

Max.

 

 

 

 

 

 

Time

Freq.

 

 

 

max.

 

 

 

P2-CM

 

ON

Time

 

 

 

FX-CM

ON

 

Time

 

 

 

RX-CM

 

ON

Time

 

 

 

 

 

[3-Wire Operation]

 

[Ext Trip-A]

This is a normally open contact input. When a terminal set to ‘Ext Trip-A’ is ON, inverter displays the fault and cuts off its output. This can be used as an external latch trip.

[Ext Trip-B]

This is a normally closed contact input. When a terminal set to ‘Ext Trip-B’ is OFF, inverter displays the fault and cuts off its output. This can be used as an external latch trip.

[Open-Loop]

This is used to exchange the control mode of inverter from PID mode (Close Loop) to V/F mode (Open Loop).

DRV-03 [Drive Mode] and DRV-04 [Frequency Mode] are applied when the mode has been changed.

Note: This function can be used only when the inverter is stopped.