Cleveland Range inverter manual Parameter Description I/O, Stall, MO-MGconfigured as ‘OL’

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 77
Image 77
[MO-MG configured as ‘OL’]

Chapter 4 - Parameter Description [I/O]

[OL]

MO-MG is CLOSED when the output current has reached the FU1-54 [Overload Warning Level] for the FU1-55 [Overload Warning Time].

Output Current

FU1-54 [OL level]

[MO-MG configured as ‘IOL’] Time

FU1-54 [OL level]

MO-MG

 

 

 

 

 

 

 

 

 

 

 

ON

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t1

 

t1

 

 

t1: FU1-55 [Overload Warning Time]

[MO-MG configured as ‘OL’]

Related Functions: FU1-54 [Overload Warning Level] FU1-55 [Overload Warning Time]

[IOL]

MO-MG is CLOSED when the output current is above the 150% of rated inverter current for 36 seconds. If this situation is continued for one minute, the inverter will cut off its output and displays ‘IOLT’ (Inverter overload trip). See the nameplate for the rated inverter current.

Output Current

150% of Rated

Inverter Current

[Stall] Time

150% of Rated

Inverter Current

MO-MG

 

 

 

 

 

 

 

ON

 

Time

 

36sec

 

 

 

 

 

 

 

 

 

 

 

 

24sec

 

[MO-MG configured as ‘IOL’]

[Stall]

MO-MG is CLOSED when the inverter is on the stall prevention mode.

Output Current

FU1-60 [Stall Level]

[MO-MG configured as ‘Stall’] Time

FU1-60 [Stall Level]

Output Frequency

Time

MO-MG

 

 

 

 

 

CLOSED

 

Time

 

 

 

 

[MO-MG configured as ‘Stall’]

Related Functions: FU1-59 [Stall Prevention Mode] FU1-60 [Stall Prevention Level]

[OV]

MO-MG is CLOSED when the DC link voltage is above the Over-voltage level.

DC Link Voltage

OV Level (380V DC or 760V DC)

MO-MG

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

Time

 

 

 

 

[MO-MG configured as ‘OV’]

71

Page 77
Image 77
Cleveland Range inverter manual Parameter Description I/O, Stall, MO-MGconfigured as ‘OL’, MO-MGconfigured as ‘IOL’