Cleveland Range inverter manual Parameter Description DRV, DRV-05~ DRV-07 Step Frequency 1 ~

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 42
Image 42
DRV-05 ~ DRV-07: Step Frequency 1 ~ 3

Chapter 4 - Parameter Description [DRV]

Output Frequency

 

 

Freq. Max

 

 

 

 

Reference Freq. Range

 

 

Analog Signal

4mA

20mA

Input (I)

 

[Freq Mode: ‘I’]

Output Frequency

 

 

Freq. Max

 

 

 

 

Reference Freq. Range

 

 

Analog Signal

0V+4mA

10V+20mA

Input (‘V1+I’)

 

 

[Freq Mode: V1+’I’]

DRV-05 ~ DRV-07: Step Frequency 1 ~ 3

The inverter outputs preset frequencies set in these codes according to the multi-function input terminals configured as ‘Speed-L’, ‘Speed-M’ and ‘Speed-H’. The output frequencies are determined by the binary combination of P1, P2, P3 configured in I/O-12 to I/O-17. Refer to the following table for the preset frequency outputs.

Speed 4 through Speed 7 is set in I/O-21~I/O-24.

Binary Combination of P1, P2, P3

Output

Step

Speed-L

Speed-M

Speed-H

Frequency

Speed

0

0

0

DRV-00

Speed 0

1

0

0

DRV-05

Speed 1

0

1

0

DRV-06

Speed 2

1

1

0

DRV-07

Speed 3

0: ON, 1: OFF

Output Frequency

Speed 0

 

 

 

Speed 3

 

 

 

Speed 2

 

 

 

Speed 1

 

 

 

 

 

 

Time

P1-CM

ON

ON

Time

 

 

 

P2-CM

 

ON

Time

 

 

 

P3-CM

 

 

Time

 

 

 

 

[Step Frequency Output]

 

Related Functions: I/O-12 to I/O-14 [Reference Inputs] I/O-17 [Filtering Time Constant]

I/O-12 to I/O-14: Set the terminal function of P1, P2, P3 terminal inputs.

I/O-17: Adjust response sensibility of input terminal to eliminate contact noise.

DRV-08: Output Current

This code displays the output current of the inverter in RMS.

DRV-09: Motor Speed

36

Page 42
Image 42