Cleveland Range inverter manual MODBUS-RTUCommunication, Request for Write, Acknowledge Response

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 85
Image 85
Request for Write

Chapter 5 - MODBUS-RTU Communication

Request for Write

 

 

 

 

 

 

 

 

The number of

 

 

 

 

 

 

 

ENQ

 

Drive No.

CMD

Address

 

address to

Data

SUM

 

EOT

 

 

 

 

 

 

 

 

 

write

 

 

 

 

 

 

 

05h

 

“01” ~ “1F”

“W”

“XXXX”

“1” ~ “8” = n

“XXXX…”

“XX”

 

04h

 

1 byte

 

2 bytes

1 byte

4 bytes

1 byte

n * 4 bytes

2

 

 

1

Total byte = 12 + n * 4 = max. 44 bytes

 

 

 

 

 

 

 

 

Acknowledge Response

 

 

 

 

 

 

 

 

 

 

ACK

Drive No.

 

CMD

 

Data

 

SUM

 

 

EOT

 

06h

 

“01” ~ “1F”

 

“W”

 

“XXXX…”

 

“XX”

 

 

04h

 

1 byte

2 bytes

 

1 byte

 

n * 4 bytes

 

2 bytes

 

 

1 byte

Total byte = 7 + n * 4 = max. 39 bytes

 

 

 

 

 

 

 

 

Negative Acknowledge Response

 

 

 

 

 

 

 

 

 

NAK

Drive No.

 

CMD

 

Error Code

 

SUM

 

 

EOT

 

15h

 

“01” ~ “1F”

 

“W”

 

“**”

 

“XX”

 

 

04h

 

1 byte

2 bytes

 

1 byte

 

2 bytes

 

2 bytes

 

 

1 byte

Total byte = 9 bytes

Note) As for Run and Frequency command, when Request for Write and Acknowledge Response is exchanged

between pc and inverter for the first time, previous data is returned. In this case, Request for Write Twice.

From the second time of transmission, the exactly same data will be transmitted.

Request for Monitor Registration: This is useful when constant parameter monitoring and data updates are required.

Request for Registration of ‘n’ numbers of Address

 

 

 

 

 

 

 

The number

 

 

 

 

 

 

ENQ

Drive No.

 

CMD

 

of address

Address

 

SUM

EOT

 

 

 

 

 

 

 

to monitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05h

“01” ~

 

“X”

 

“1” ~

“XXXX…”

 

“XX”

04h

1 byte

2 bytes

 

1 byte

 

1 byte

 

n * 4

 

2 bytes

1 byte

Total byte = 8 + n * 4 = max. 40 bytes

 

 

 

 

 

 

 

Acknowledge Response

 

 

 

 

 

 

 

 

 

 

ACK

 

Drive No.

 

CMD

 

SUM

 

 

EOT

06h

 

“01” ~ “1F”

 

“X”

 

“XX”

 

 

04h

1 byte

 

2 bytes

 

1 byte

 

2 bytes

 

 

1 byte

Total byte = 7 bytes

79

Page 85
Image 85
Cleveland Range inverter manual MODBUS-RTUCommunication, Request for Write, Negative Acknowledge Response