Chapter 4 - Parameter Description [FU2]

Chapter 4 - Parameter Description [FU2]

4.3 Function 2 Group [FU2]

FU2-00: Jump to Desired Code #

Jumping directly to any parameter code can be accomplished by entering the desired code number.

FU2-01: Previous Fault History 1

FU2-02: Previous Fault History 2

FU2-03: Previous Fault History 3

FU2-04: Previous Fault History 4

FU2-05: Previous Fault History 5

FU2-06: Erase Fault History

This code displays up to five previous fault (trip) status of the inverter. Use the [FUNC], [▲] and [▼] key before pressing the [RESET] key to check the fault content(s), output frequency, output current, and whether the inverter was accelerating, decelerating, or in constant speed at the time of the fault occurred. Press the [FUNC] key to exit. The fault content will be stored in FU2-01 through FU2-05 when the [RESET] key is pressed. For more detail, please refer to Chapter 7.

[Fault Contents]

Fault (Trip)

Keypad Display

Over-Current 1

OC

Over-Voltage

OV

Emergency Stop

BX

(Not Latched)

 

Low-Voltage

LV

Ground Fault

GF

Over-Heat on Heat sink

OH

Electronic Thermal Trip

ETH

Over-Load Trip

OLT

Inverter H/W Fault

HW

Output Phase Loss

OPO

Input Phase Loss

COL

Inverter Over-Load

IOLT

Note: There is Fan error, EEP error, CPU2 error, Ground fault and NTC error for the inverter Hardware Fault. The inverter will not reset when H/W fault occurs. Repair the fault before turning on the power.

Note: When multiple faults occur, only the highest-level fault will be displayed.

Related Functions: DRV-12 [Fault Display] displays current fault status.

This function erases all fault histories of FU2-01 to FU-05 from the memory.

FU2-07: Dwell Frequency

FU2-08: Dwell Time

This function is used to output torque in an intended direction. It is useful in hoisting applications to get enough torque before a