FU2-22: Speed Search Selection (Bit Set)

Chapter 4 - Parameter Description [FU2]

Output Frequency

Tripped

FU2-24: P Gain During Speed Search Time

Start

 

 

 

 

 

 

FX-CM

 

ON

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RST-CM

 

ON

 

 

Time

 

 

 

 

[Reset restart: ‘Yes’]

Note: In case of using ‘Reset Restart’ to ‘Yes’, make sure to utilize appropriate warning notices to minimize the potential for injury or equipment damage.

Related Functions: FU2-22 ~ FU2-25 [Speed Search]

FU2-22: Speed Search Selection (Bit Set)

FU2-23: Current Limit Level During Speed Search

FU2-24: P Gain During Speed Search

FU2-25: I Gain During Speed Search

This function is used to permit automatic restarting after Power ON, Fault Reset, and Instant Power Failure without waiting for the motor to stop.

The speed search gain should be set after considering the inertia moment (GD2) and magnitude of torque of the load. FU2-37 [Load

Inertia] must be set at the correct value to make this function operate correctly.

FU2-22 [Speed Search Select]

 

Setting Range

 

Description

4th bit

 

3rd bit

2nd bit

 

1st bit

 

 

 

0

 

0

0

 

0

Speed search function does not work

0

 

0

0

 

1

Speed search during Accelerating

 

 

 

 

 

 

Speed search during a Fault Reset

0

 

0

1

 

0

restarting (FU2-21) and Auto restarting

 

 

 

 

 

 

(FU2-26)

0

 

1

0

 

0

Speed search during Instant Power

 

 

Failure restarting.

1

 

0

0

 

0

Speed search during Power ON

 

 

starting (FU2-20)

When FU2-22 is set to ‘1111’, Speed Search works for all conditions.

FU2-22[Speed Search Selection] selects the speed search function.

FU2-23[Current Limit Level] is the current that the inverter limits its current rise during speed searching. (The set value is the percentage of FU2-33 [Rated Motor Current])

FU2-24[P Gain] is the proportional gain used for speed search. Set this value according to load inertia set in FU2-37.

FU2-25[I Gain] is the Integral gain used for speed search. Set this value according to load inertia set in FU2-37.