Chapter 2 - Operation

Chapter 2 - Operation

2.2 Parameter Setting and Change

Numerous parameters are built into the inverter. The keypad allows the operator to operate the inverter by setting the required parameters, and enter the proper value according to the load and operating conditions. Refer to Chapter 4 ‘PARAMETER DESCRIPTION’ for detailed description of the functions.

Procedures

First move to the group code that needs changing. Press [FUNC] key. The keypad LED (SET) will turn ON.

Use the [(Up)], [(Down)] keys to set the data to the desired value.

Press [FUNC] key again. The data display will blink and the data will be stored in the inverter.

Note: If the data does not changed, determine if:

-Inverter is running (Refer to the function table in Chapter 3)

-Function is locked in H 94 [Parameter Lock]

Setting the DRV Group Data

Example) Change the acceleration time from 60 sec to 40 sec:

SET

RUN

SET

RUN

2.2 Parameter Setting and ChangeManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background FWD FUNC SET Manual backgroundManual background

REV RUN

Manual background FWD

REV

Manual background FWD Manual background SET Manual background

REV RUN

FUNC

Manual background FWD

REV

Data will blink when the data setting is finished. Indicates data programming is complete.

To Monitor Current Output from the DRV Group Example) Monitor current output from inverter (Data cannot be set):

SET

RUN

Manual backgroundManual backgroundManual backgroundManual backgroundManual background FWD FUNC SET Manual backgroundManual background

REV RUN

Manual background FWD FUNC SET

REV RUN

Manual background FWD

REV

17

Page 23
Image 23
Cleveland Range inverter manual Parameter Setting and Change, Operation