Cleveland Range inverter manual Troubleshooting & Maintenance, Condition, Check Point

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 100
Image 100
6.4 Troubleshooting

Chapter 6 - Troubleshooting & Maintenance

6.4 Troubleshooting

 

Condition

 

 

Check Point

 

 

 

 

1)

Main circuit inspection

 

 

 

 

 

Input (line) voltage normal? (LED charge lamp on?)

 

 

 

 

 

Motor connected correctly?

 

 

 

 

2)

Input signal inspection

 

 

 

 

 

Input signal to inverter functioning?

 

 

 

 

 

Forward and reverse signals inputted simultaneously to inverter?

 

 

The motor does

 

 

Inverter receiving command input frequency signal?

 

 

 

3)

Parameter setting inspection

 

 

not rotate

 

 

 

 

 

Reverse prevention (FU1-03) function set?

 

 

 

 

 

 

 

 

 

 

Operation mode (FU1-01) set correctly?

 

 

 

 

 

Command frequency set to 0?

 

 

 

 

4) Load inspection

 

 

 

 

 

Load too large, or motor restrained. (Mechanical Brake)

 

 

 

 

5) Other

 

 

 

 

 

Alarm displayed on keypad, or alarm LED lit? (STOP LED blinking?)

 

 

The motor rotates

 

Phase sequence of output terminal U, V and W correct?

 

 

in opposite

 

Starting signal (Forward/Reverse) connected correctly?

 

 

directions

 

 

 

 

 

The difference

 

Reference frequency verified? (Check the level of input signal)

 

 

between the

 

Following parameter setting verified?

 

 

rotating speed and

 

 

Lower Limit Frequency (FU1-24), Upper Limit Frequency (FU1-25), Analog Frequency Gain (I/O-

 

 

the reference is

 

 

1~10)

 

 

too big

 

External noise? (Use a shielded wire)

 

 

The inverter does

 

Acceleration/Deceleration time too short.

 

 

not accelerate or

 

Load too large?

 

 

decelerate

 

Torque Boost (FU1-27, 28) value too high? (Current limit function and the stall prevention

 

 

smoothly

 

 

function verified?)

 

 

The motor current

 

Load too large?

 

 

is too high

 

Torque Boost Value (manual) too high?

 

 

The rotating

 

Upper Limit Frequency (FU1-25) value correct?

 

 

speed does not

 

Load too large?

 

 

increase

 

Torque Boost (FU1-27, 28) value too high? Is Stall prevention function (FU1-59, 60) verified?

 

 

 

 

1)

Load inspection

 

 

The rotating

 

 

Load oscillating?

 

 

speed oscillates

 

2)

Input signal inspection

 

 

when the inverter

 

 

Reference frequency signal oscillating?

 

 

is operating.

 

3)

Other

 

 

 

 

 

Wiring too long? (Over 500m, 1,500ft)

 

94

Page 100
Image 100
Cleveland Range inverter manual Troubleshooting & Maintenance, Condition, Check Point