Cleveland Range inverter manual Parameter List, Volts/Hz Pattern

Models: inverter

1 119
Download 119 pages 48.5 Kb
Page 32
Image 32
Volts/Hz Pattern

Chapter 3 - Parameter List

 

 

Keypad

 

 

Factory

Adj.

 

Code

Description

Setting Range

Units

During

Page

Display

Default

 

 

 

 

Run

 

 

 

 

 

 

 

 

FU1-29

Volts/Hz Pattern

F 29

0 (Linear)

-

0 (Linear)

No

44

1 (Square)

 

 

 

2 (User V/F)

 

 

 

 

FU1-309

User V/F – Frequency 1

F 30

0.00 to (FU1-32)

0.01

15.00 [Hz]

No

 

FU1-31

User V/F – Voltage 1

F 31

0 to 100 [%]

1

25 [%]

No

 

FU1-32

User V/F – Frequency 2

F 32

(FU1-30) to (FU1-34)

0.01

30.00 [Hz]

No

 

FU1-33

User V/F – Voltage 2

F 33

0 to 100 [%]

1

50 [%]

No

44

FU1-34

User V/F – Frequency 3

F 34

(FU1-32) to (FU1-36)

0.01

45.00 [Hz]

No

 

FU1-35

User V/F – Voltage 3

F 35

0 to 100 [%]

1

75 [%]

No

 

FU1-36

User V/F – Frequency 4

F 36

(FU1-34) to (FU1-20)

0.01

50 / 60 [Hz]

No

 

FU1-37

User V/F – Voltage 4

F 37

0 to 100 [%]

1

100 [%]

No

 

FU1-38

Output Voltage Adjustment

F 38

40 to 110 [%]

0.1

100.0 [%]

No

45

FU1-39

Energy Save Level

F 39

0 to 30 [%]

1

0 [%]

Yes

45

FU1-50

Electronic Thermal Selection

F 50

0 (No)

-

0 (No)

Yes

 

1 (Yes)

 

 

 

 

 

 

 

 

FU1-5110

Electronic Thermal Level for 1 Minute

F 51

FU1-52 to 250 [%]

1

180 [%]

Yes

 

FU1-52

Electronic Thermal Level for

F 52

50 to FU1-51

1

120 [%]

Yes

46

Continuous

 

 

FU1-53

Electronic Thermal Characteristic

F 53

0 (Self-cool)

-

0 (Self-cool)

Yes

 

 

 

 

Selection (Motor type)

 

1 (Forced-cool)

 

 

 

 

FU1-54

Overload Warning Level

F 54

30 to 250 [%]

1

150 [%]

Yes

47

FU1-55

Overload Warning Hold Time

F 55

0 to 30 [sec]

0.1

10.0 [sec]

Yes

 

FU1-56

Overload Trip Selection

F 56

0 (No)

-

1 (Yes)

Yes

 

1 (Yes)

47

 

 

 

 

 

 

FU1-5711

Overload Trip Level

F 57

30 to 250 [%]

1

200 [%]

Yes

 

FU1-58

Overload Trip Delay Time

F 58

0 to 60 [sec]

1

60.0 [sec]

Yes

 

 

 

 

000 – 111 (bit set)

 

 

 

 

FU1-59

 

F 59

Bit 0: during Accel.

 

 

 

 

Stall Prevention Mode Selection

Bit 1: during Steady

bit

000

No

48

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2: during Decel.

 

 

 

 

FU1-60

Stall Prevention Level

F 60

30 to 250 [%]

1

200 [%]

No

 

FU1-99

Return Code

rt

 

-

-

-

49

9Code FU1-30 through FU1-37 appears only when FU1-29 is set to ‘User V/F’.

10Code FU1-51 through FU1-53 appears only when FU1-50 is set to ‘Yes’.

11Code FU1-57 through FU1-58 appears only when FU1-56 is set to ‘Yes’.

26

Page 32
Image 32
Cleveland Range inverter manual Parameter List, Volts/Hz Pattern