41
C4 Manual Rev 7.5.2
5. LOCAL MODE ( Basic Operation )
The C4 Local mode of operation provides simple control of the chamber or
platform through the front panel controls. In this mode, a single setpoint is
entered from the front panel and the controller will attempt to have the chamber
or platform reach and hold that temperature. In local mode the compressor of
mechanically refrigerated units can be turned on or off using the <REFER> button
on the front panel.
The controller can be set to automatically start controlling at the last used
temperature upon startup by setting the controller to the AutoStart mode. See
AutoStart mode description, Section 8.4.
The circled numbers on the front panel guide the user through the sequence for
the basic operation of changing the setpoint. The reasoning for each keystroke is
as follows:
1. Display control setpoint temperature.
2. Clear the existing setpoint value.
3. Key-in control probe number (only if 2 probes defined in setup parameter
F1) & new setpoint.
4. Commit new setpoint entry.
5. Display current chamber temperature.
If controller RUN LED is not ON press <START/STOP> to begin controlling
at set temperature.
5.1 Displaying Temperature
The temperature may be displayed at any time by pressing the <DISP/TEMP> key.
The format of the display is
Pn TT.T Example: p1 - 102.6 (Celsius)
PnF-TTT.T Example: p1f- 102.6 (Fahrenheit)
where n indicates from which probe the reading originates and the -TTT.T
indicates the numeric temperature. In single probe mode, n is always 1. In two