<In heating operation> (Heat pump model)

Item

 

Operation flow and applicable data, etc.

 

Description

 

 

 

 

2. Indoor fan

<In heating operation> (Heat pump model)

 

1) When setting the fan speed to

motor control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L, L+, M, M+ or H on the remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller, the operation is

 

 

HEAT ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

performed with the constant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed shown in Fig. 3 and Table 1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) When setting the fan speed to

 

Fan speed setup

 

 

MANUAL

 

 

 

 

AUTO on the remote controller,

 

 

 

 

(Fig. 3)

 

revolution of the fan motor is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controlled to the fan speed level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shown in Fig. 5 according to the

 

 

 

 

 

 

 

 

 

Indication

 

Fan speed

 

 

 

 

 

 

 

 

 

 

 

set temperature and room

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

W8

 

temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Min air flow rate is controlled by

 

 

 

 

 

 

 

 

 

L+

 

(L + M) / 2

 

 

 

 

 

 

 

 

 

 

 

 

 

AUTO

 

 

 

 

 

 

 

 

 

 

 

temperature of the indoor heat

 

 

 

 

 

 

M

 

WB

 

 

 

 

 

 

 

 

 

 

 

 

exchanger (Tc) as shown in Fig. 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M+

 

(M + H) / 2

 

4) Cold draft prevention, the fan

 

 

 

 

 

 

 

 

 

H

 

WE

 

speed is controlled by tempera-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ture of the indoor heat ex-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

changer (Tc) as shown in

 

 

TC 42˚C

 

 

 

 

 

Min air flow rate control

 

 

Fig. 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tc

 

Limited to Min WD tap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

 

*

 

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

No limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Fan speed =

(TC – (42 + a)) / 10 x (WD – W8) + W8

 

 

a : In up operation 1, in down operation 0

(Fig. 4)

 

Basic fan control

Fan speed

 

Cold draft preventive control

TA [˚C]

b

AUTO

 

 

 

 

TSC

 

 

Tc

 

 

 

L (W8)

 

 

 

 

c

 

 

 

–0.5

 

46

46

34

H (WE)

 

 

45

45

33

 

d

*1

 

–1.0

 

 

 

 

 

 

 

 

Line-approximate

 

 

 

 

 

 

e

*2

33

33

21

H and SUL with Tc.

–1.5

 

 

 

32

32

20

 

 

f

 

 

–2.0

*3

 

 

 

 

 

*A+4

*A+4

*A+4

 

 

 

 

 

–2.5

g

 

*A-4

*A-4

*A-4

SUL (W2)

 

 

 

 

 

 

Stop

–5.0

 

M+ (WD)

 

 

 

 

Fan speed Fan speed Fan speed

 

 

 

 

 

–5.5

 

 

AUTO

AUTO

MANUAL

 

 

H (WE)

in starting in stability in starting

 

 

 

 

 

 

 

*1: Fan speed = (M + –L) x 1 4 + L

 

* No limitation while fan speed MANUAL mode is in stability.

*2: Fan speed = (M + –L) x 2 4 + L

 

 

* A: When Tsc 24, A is 24, and when Tsc < 24, A is Tsc

*3: Fan speed = (M + –L) x 3 4 + L

 

 

Tsc: Set value

 

 

(Calculated with linear approximation from M+ and L)

 

 

 

 

 

 

 

(Fig. 5)

(Fig. 6)

[In starting and in stability]

 

 

 

 

 

In starting

In stability

 

 

 

FAN AUTO

• Until 12 minutes passed after operation start

• When 12 to 25 minutes passed after operation start and

 

• When 12 to 25 minutes passed after operation start

room temp. is higher than (set temp. –3°C)

 

and room temp. is 3°C or lower than set temp.

• When 25 minutes or more passed after operation start

 

 

 

FAN Manual

• Room temp. < Set temp. –4°C

• Room temp.Set temp. –3.5°C

 

 

 