Toshiba RAS-M16EKCVP-E 84, Block distinction, Operation of diagnosis function, Cause of operation

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 84
Image 84
Operation of diagnosis function

Block distinction

 

Operation of diagnosis function

 

 

 

 

 

 

 

 

 

 

Check

 

Check

 

Air

 

 

Judgment and action

Block

Cause of operation

conditioner

Remarks

 

code

code

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor P.C.

 

Current-detect circuit

All off

Displayed when

Even if trying operation again, all

 

board

 

error

 

error is detected.

operations stop immediately. :

 

 

 

 

 

 

Replace P.C. board.

 

 

 

 

 

 

 

 

 

 

Being out of place,

All off

Displayed when

Check 5-serial LED.

 

 

 

disconnection or short-

 

error is detected.

1.

Check outdoor temp. sensors

 

 

 

circuit of outdoor temp.

 

 

 

(TE, TS).

 

 

 

sensor (Ts)

 

 

2.

Check P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Disconnection or short-

All off

Displayed when

1.

Check discharge temp. sensor

 

 

 

circuit of discharge

 

error is detected.

 

(TD).

 

 

 

temp. sensor

 

 

2.

Check P.C. board

 

 

 

 

 

 

 

 

 

 

Outdoor fan drive

All off

Displayed when

Position-detect error, over-current

 

 

 

system error

 

error is detected.

protective operation of outdoor fan

 

 

 

 

 

 

drive system, fan lock, etc. :

 

 

 

 

 

 

Replace P.C. board or fan motor.

 

 

 

 

 

 

 

 

 

Not

 

Outdoor temp. sensor

Operation

 

1.

Check outdoor temp. sensor

 

displayed

 

error

continues

——

 

(TO).

 

 

 

 

 

 

2.

Check P.C. board.

 

 

 

 

 

 

 

 

Outdoor P.C.

 

Compressor drive

All off

Displayed when

Check 5-serial LED.

 

board

 

output error, Compres-

 

error is detected.

When 20 seconds passed after

 

 

 

sor error (lock, missing,

 

 

start-up, position-detect circuit

 

 

 

etc.), Break down

 

 

error occurred. : Replace

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

Error exclusive for

All off

Displayed when

Check 5-serial LED.

 

 

 

multiple type

 

error is detacted.

1.

Miswiring of connecting wire of

 

 

 

 

 

 

 

A/B rooms in indoor/outdoor

 

 

 

 

 

 

 

units

 

 

 

 

 

 

2.

Check gas leakage.

 

 

 

 

 

 

3.

Check disconnection of sensor.

 

 

 

 

 

 

4.

Electronic control valve error

 

 

 

 

 

 

 

 

 

Others

 

Return serial signal has

Operation

Flashes when

1.

Repeat Start and Stop with

 

(including

 

been sent when

continues

trouble is detected

 

interval of approx. 10 to 40

 

compres-

 

operation started, but it

 

on return serial

 

minutes. (Code is not displayed

 

sor)

 

is not sent from

 

signal, and normal

 

during operation.)

 

 

 

halfway.

 

status when signal

 

Supply gas. (Check also gas

 

 

 

(1) Compressor thermo.

 

is reset.

 

leak).

 

 

 

operation

 

 

2.

Unit operates normally during

 

 

 

Gas shortage

 

 

 

check.

 

 

 

Gas leak

 

 

 

If return serial signal does not

 

 

 

(2) Instantaneous

 

 

 

stop between indoor terminal

 

 

 

power failure

 

 

 

block 2 and 3, replace inverter

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

If signal stops between indoor

 

 

 

 

 

 

 

terminal block 2 and 3, replace

 

 

 

 

 

 

 

indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Compressor does not

All off

Displayed when

1.

Trouble on compressor

 

 

 

rotate.

 

error is detected.

2.

Trouble on wiring of compres-

 

 

 

(Current protective

 

 

 

sor (Missed phase)

 

 

 

circuit does not operate

 

 

 

 

 

 

 

when a specified time

 

 

 

 

 

 

 

passed after compres-

 

 

 

 

 

 

 

sor had been acti-

 

 

 

 

 

 

 

vated.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge temp.

All off

Displayed when

1.

Check dischage temp. sensor

 

 

 

exceeded 117°C

 

error is detected.

 

(TD).

 

 

 

 

 

 

2.

Gas leakage

 

 

 

 

 

 

3.

Trouble on P.M.V.

 

 

 

 

 

 

 

 

 

 

 

Break down of

All off

Displayed when

1.

Check power voltage.

 

 

 

compressor

 

error is detected.

 

(220–230–240 V +10%)

 

 

 

 

 

 

2.

Overload operation of refrigera-

 

 

 

 

 

 

 

tion cycle

 

 

 

 

 

 

 

Check installation condition

 

 

 

 

 

 

 

(Short-circuit of outdoor diffuser).

 

 

 

 

 

 

 

 

– 84 –

Page 84
Image 84
Toshiba RAS-M16EKCVP-E 84, Block distinction, Operation of diagnosis function, Judgment and action, Cause of operation